Motor Protection - Trane Starters Engineering Bulletin

Starters; electrical components; drives for centravac chillers
Table of Contents

Advertisement

Motor Protection

Historically, motor protection was provided in the starter by some type of monitoring system.
Starter manufacturers usually provide a full range of optional equipment mounted on the starter.
Eaton Cutler-Hammer
Today,Trane provides most of the key motor protection and metering functions (see
column) within the chiller microprocessor control panel as standard. Having the motor control and
chiller control in one panel provides better integration and optimization of the two control systems.
For example, the chiller controller can unload the chiller when approaching an overload "trip"
point, so that the chiller stays online.
Table 2
controller with those of other common Eaton Cutler-Hammer
Additional starter-mounted metering and motor protection may not be required and could be
considered redundant.These devices are not available for AFDs.
Table 2.
Protection and functions by motor packages
Protection Functions
Communications
Ground fault
Long acceleration
Maximum number of starts
Momentary power loss (distribution fault)
Motor overload
Motor winding temperature
Over temperature
Overvoltage
Phase imbalance
Phase loss
Phase reversal
Run timer
(f)
Separate alarm levels
Surge capacitor/lightning arrestor
Undervoltage
(a) The MP 3000 features Intel-I-Trip overload protection, enhanced custom trip curve development, UL 1053 ground fault, and advanced data logging and
diagnostics.
(b) For low voltage, a Trane-supplied circuit breaker or non-fused disconnect is also required when ground fault is specified.
(c) The chiller controller monitors the motor temperatures of all three phases with one resistance temperature detector (RTD) per phase
(d) For this option, add one or two sets (three RTDs per set) of 100-ohm platinum RTDs to the motor. Contact La Crosse Field Sales Support.
(e) Under/over phase-voltage sensors include volts per phase, kW, power factor, kWh, and under/overvoltage. A required pick on medium-voltage starters.
(f) Three alarm levels are used: warning only, nonlatching (auto-reset), and latching (manual reset required).
CTV-PRB004-EN
®
offers IQ metering and motor protection products for their starters.
and
Table 3, p. 14
can be used to compare the standard electrical features of the chiller
Tracer
AdaptiView
Optional
(b)
Optional
Standard
Standard
Standard
Standard
(c)
Standard
Standard
(e)
Standard
Standard
Standard
Standard
Standard
Standard
Optional
(e)
Standard
(a)
MP 3000
IQ 150
Optional
Optional
Standard
N/A
Standard
N/A
Standard
N/A
N/A
N/A
Standard
N/A
(d)
Optional
N/A
N/A
N/A
N/A
N/A
Standard
N/A
Standard
N/A
N/A
N/A
Standard
N/A
Standard
N/A
N/A
N/A
N/A
N/A
Table
®
starter-only-mounted devices.
IQ DP 4130
Optional
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Standard
Standard
Standard
Standard
N/A
N/A
N/A
Standard
2, first
13

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Electrical componentsDrivesCvheCvhfCvhgCdhf ... Show all

Table of Contents