Trane Starters Engineering Bulletin page 30

Starters; electrical components; drives for centravac chillers
Table of Contents

Advertisement

Low-Voltage Starter Types
Environmental specification
Dimensions
Table 6
and use theTrane submittals for actual dimensions.
Table 6.
Remote AFD dimensions
460 Vac
Frame
Power (hp)
D3/D4
150–350
E2
450–600
N/A
F3
650–750
950–1050
F4
1150–1350
Digital data display
The following points are digitally displayed at the chiller controller:
Harmonics
The remote AFD is a standard six pulse design.Therefore the harmonic level is ~35 percent total
demand distortionTDD as measured at the AFD input. If lower levels of attenuation are required,
upstream filtering would be required.
30
Operating temperature: 32°F to 104°F (0°C to 40°C).
Storage temperature: -4°F to 149°F (-20°C to 65°C).
Humidity: 95 percent non-condensing.
Maximum elevation: 3280 ft (1000 m) rated output current.
Derate 4 percent/3280 ft over rated altitudes up to 9840 ft (3000 m).
provides some basic reference dimensions and weights for the remote AFD. Always refer
575 Vac
Max. Amps
Power (hp)
394
150–400
649
450
N/A
500–650
791
750–1050
1031
N/A
1360
1150–1550
Frequency command
Input line voltage
Load-side amps
Max. Amps
Width (in.)
356
48
400
56
560
64
840
127
N/A
127
1258
150
Depth (in.)
Height (in.) Weight (lb)
24
86
24
90
24
90
24
90
24
90
24
90
CTV-PRB004-EN
1220
1635
1680
2885
3185
3720

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Electrical componentsDrivesCvheCvhfCvhgCdhf ... Show all