Diagnostics
Comm Loss: Evaporator Water
Flow Switch
Comm Loss: Evaporator Water
Flow Switch
Comm: Evap Water Flow Sw
Comm Loss: Local BAS Interface
Comm Loss: Local BAS Interface
Comm: Local BAS Interface
Comm Loss: Compressor Fault
Input
Comm Loss: Compressor Fault
Input
Comm: Compressor Fault
Input
Comm Loss: Compressor Run
Command
Comm Loss: Compressor Run
Command
Comm: Cprsr Run Command
Comm Loss: Fan Control Relays
Comm Loss: Fan Control Relays
Comm: Fan Control Relays
Comm Loss: Fan Fault
Comm Loss: Fan Fault
Comm: Fan Fault
Comm Loss: Fan Inverter Speed
Command
Comm Loss: Fan Inverter Speed
Command
Comm: Fan Inverter Speed
Cmd
Comm Loss: Fan Inverter Fault
Comm Loss: Fan Inverter Fault
Comm: Fan Inverter Fault
Comm Loss: Op Status
Programmable Relays
Comm Loss: Op Status
Programmable Relays
Comm: Op Status Relays
Comm Loss: Anti-Freeze Heater
Relay
Comm Loss: Anti-Freeze Heater
Relay
Comm: Anti-Freeze Heater
Rly
Comm Loss: Evaporator Water
Pump 1 Relay
Comm Loss: Evaporator Water
Pump 1 Relay
Comm: Evap Water Pump
Relay
178
Chiller
Immediate
Latch
Warning and
Chiller
Special
NonLatch
Action
Cprsr
Immediate
Latch
Cprsr
Immediate
Latch
Circuit
Immediate
Latch
Circuit
Warning
Latch
Warning and
Circuit
Special
NonLatch
Action
Warning and
Circuit
Special
Latch
Action
Chiller
Warning
Latch
Warning and
Chiller
Special
Latch
Action
Chiller
Normal
Latch
Continual loss of communication
All
between the MP and the Functional ID
has occurred for a 35-40 second period.
Continual loss of communication
between the MP and the Functional ID
All
has occurred for a 35-40 second period.
Use the last values sent from BAS.
Continual loss of communication
All
between the MP and the Functional ID
has occurred for a 35-40 second period.
Continual loss of communication
All
between the MP and the Functional ID
has occurred for a 35-40 second period.
Continual loss of communication
All
between the MP and the Functional ID
has occurred for a 35-40 second period.
Continual loss of communication
All
between the MP and the Functional ID
has occurred for a 35-40 second period.
Continual loss of communication
between the MP and the Functional ID
All
has occurred for a 35-40 second period.
Revert to fixed-speed fan algorithm
using remaining fans.
Continual loss of communication
between the MP and the Functional ID
All
has occurred for a 35-40 second period.
Revert to fixed-speed fan algorithm
using remaining fans.
Continual loss of communication
All
between the MP and the Functional ID
has occurred for a 35-40 second period.
Continual loss of communication
All
between the MP and the Functional ID
has occurred for a 35-40 second period.
Continual loss of communication
All
between the MP and the Functional ID
has occurred for a 35-40 second period.
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
CG-SVX17D-EN