Product Information

The benefits at a glance:
Easy and uniform operation:
H
Different programming levels for
system user and heating contractor.
Large, clear text LCD display format
facilitates legibility of all data.
Illuminated operating mode and
heating circuit keys.
Easy-to-program switching times.
Digital tracking of day and week.
Programmed times for domestic hot
water production and recirculation
pump are adjusted automatically
when heating program is altered.
Plug & Work quick-connect system for
automatic sensor and system
recognition and adaptation.
Automatic resetting to daylight
savings time.
Service interval display for
demand-related maintenance.
Fuel consumption display.
Program selection for controlled drying
H
of concrete floor in radiant floor heating
application.
Short installation time, start-up and
H
maintenance due to Rast-5 connector
system, plug-in function modules and
integrated diagnostic system
Application
In conjunction with the following Viessmann boilers
Boiler Model and Series
Oil-fired hot water
Vitorond 200
heating boiler with
power burner
Oil-/gas-fired hot water
Vitola 200
heating boiler with
power burner
Atmospheric
Vitogas 050, RS Series
gas-/propane-fired hot
water heating boiler
Atmospheric gas-fired
Vitogas 100, GS1 up to 240 MBH / 70 kW
hot water heating boiler
Vitogas 100, GS10 up to 380 MBH / 111 kW
2
Vitotronic 200, Model KW2
OTS
Weather-responsive indoor/outdoor,
H
digital boiler and heating system
control:
for heating systems with one boiler
for heating circuits without and
heating circuits with a mixing valve
for single-stage, 2-stage and
modulating burners
with DHW tank temperature sensor
with digital tracking of day and week
with separate switching times for
room heating, domestic hot water
heating and recirculation pump
with integrated diagnostic system
.
STS
Fuel
Oil
Oil/Gas
Gas
Gas
Gas

Standard Equipment

Vitotronic 200, Model KW2
(Part No. Z001 230)
with
operating module with clear text LCD
H
display
outdoor temperature sensor
H
boiler water temperature sensor
H
DHW tank temperature sensor
H
Power/Pump Module
H
For the heating circuit with a mixing
valve, a mixing valve actuator accessory
kit is required. Due to the low return
water temperature of condensing boilers
only 3-way mixing valves should be
installed. The circulation pump with a
flow check valve for DHW tank
temperature control must be ordered
separately.
Heating system with underfloor heating
The underfloor heating circuit requires an
accessory kit for operation with a mixing
valve.
A temperature control with high limit
must be installed in the heating supply of
the radiant floor heating application.
The underfloor heating circuit must not
be controlled by a remote control with
room temperature sensor.
Minimum boiler water
temperature
without low
with low limit
limit
(average temp.)
104 ºF/40 ºC
x
120 ºF/49 ºC
104 ºF/40 ºC
120 ºF/49 ºC