INSTALLER SYSTEM-TEST

Use the Installer System-Test to check the thermostat
configurations and operation. Refer to Table 3 for a list of
the available system-tests.
To start the system-test:
NOTE: The minimum off time for compressors is
bypassed during the Installer System-Test.
Press and hold the increase
the same time, until two zeros appear. All segments of the
LCD are displayed before the two zeros appear.
Em Ht Temporary Setting
Aux Ht
Repl
Wait
Batt
System
Em HeatOffCool Auto Only
TEST NUMBER
Key To
Test
Press
Number
Heating Equipment System-Test
i
10
11
12
11
10
Emergency Heating Equipment System-Test
i
20
b
21
b
20
Cooling Equipment System-Test
i
30
31
30
a
Available on select models.
b
T8511R models with fixed emergency heat output will not respond to this key press.
T8511G,R MICROELECTRONIC HEAT PUMP THERMOSTATS
and decrease
keys, at
Remote
Room
%Humid
Outdoor
Heat Cool
Fan
OnAuto
M4844
M6792
Table 4. Installer System-Test Options.
Enter heating equipment system-test. (Set T8511R system switch to HEAT and fan switch to
AUTO.)
Stage-one heat comes on. The system fan is also energized.
Stage-two heat comes on. Stage-one heat and system fan remain on.
Stage-two heat turns off.
Stage-one heat and system fan turn off.
a
Change from heating to emergency heating equipment system-test.
(Set T8511R system switch to EM. HT.)
Emergency heat comes on. System fan also comes on.
Emergency heat turns off. (Set T8511R system switch to OFF.)
Change from heating or emergency heating to cooling equipment system-test.
(Set T8511R system switch to COOL.)
Stage-one cooling and system fan come on.
Stage-one cool and system fan turn off.
NOTE: Press and hold the increase
keys for three seconds to exit the system-test.
The system-test times out after five minutes
without any key presses.
Table 3. Tests Available in the Installer System-Test.
Test
Number
10-19
Heating equipment can be turned on and off
20-29
Emergency heat (select models) equipment
can be turned on and off
30-39
Cooling equipment can be turned on and off
40-49
Fan equipment can be turned on and off
60-69
System key or system switch position test
70-79
Thermostat information including date code
and software versions are displayed
Refer to Table 4 for the directions and results of the
specific tests.
Description
7
and decrease
System-Test Description
(Continued)
69-0927—4