Honeywell Tradeline Chronotherm IV Installation Instructions Manual
Honeywell Tradeline Chronotherm IV Installation Instructions Manual

Honeywell Tradeline Chronotherm IV Installation Instructions Manual

Deluxe programmable heat pump thermostats

Advertisement

APPLICATION
The T8611G Chronotherm® IV Deluxe Programmable Heat Pump Thermostats provide electronic control of 24 Vac
single-zone heat pump systems. Refer to Table 1 for a general description of the thermostats. All T8611 thermostats
require a common wire to supply power.
T8611
Changeover
G
Automatic
RECYCLING NOTICE
If this control is replacing a control that contains
mercury in a sealed tube, do not place your old
control in the trash.
Contact your local waste management authority
for instructions regarding recycling and the proper
disposal of the old thermostat.
INSTALLATION
When Installing this Product...
1. Read these instructions carefully. Failure to follow
the instructions can damage the product or cause
a hazardous condition.
2. Check the ratings given in the instructions and on
the product to make sure the product is suitable for
your application.
3. Installer must be a trained, experienced service
technician.
4. After completing installation, use these instructions
to check out the product operation.
Location
Install the thermostat about 5 ft (1.5m) above the floor in
an area with good air circulation at average temperature.
See Fig. 1.
Do not install the thermostat where it can be affected by:
— drafts, or dead spots behind doors and in corners.
— hot or cold air from ducts.
— radiant heat from sun or appliances.
— concealed pipes and chimneys.
— unheated (uncooled) areas such as an outside wall
behind the thermostat.
®U.S. Registered Trademark
Copyright © 1997 Honeywell Inc. •
T8611G Chronotherm
Heat Pump Thermostats
Table 1. Description of T8611 Thermostats.
System Selection
Em Heat-Heat-Off-Cool-
Auto
• All Rights Reserved
Deluxe Programmable
Fan Selection
On-Auto
System and fan selections are done by keyboard.
Wallplate Installation
The thermostat can be mounted horizontally on the wall
or on a 2 in. x 4 in. wiring box. Position wallplate
horizontally on the wall or on a 2 in. x 4 in. wiring box.
1. Position and level the wallplate (for appearance
only). The thermostat will function properly even
when not level.
2. Use a pencil to mark the mounting holes. See
Fig. 2.
3. Remove the wallplate from the wall and drill two
3/16 inch holes in the wall (if drywall) as marked.
For firmer material such as plaster, drill two 7/32
inch holes. Gently tap anchors (provided) into the
drilled holes until flush with the wall.
4. Position the wallplate over the holes, pulling wires
through the wiring opening.
5. Loosely insert the mounting screws into the holes.
6. Tighten mounting screws.
WIRING
All wiring must comply with local electrical codes and
ordinances. Refer to Fig. 3 for typical hookup. A letter
code is located near each terminal for identification.
CAUTION
Disconnect power before wiring to prevent
electrical shock or equipment damage.
1. Loosen the terminal screws on the wallplate and
connect the system wires. See Fig. 4.
X-XX UL
INSTALLATION INSTRUCTIONS
Comments
®
IV
69-0936-1

Advertisement

Table of Contents
loading

Summary of Contents for Honeywell Tradeline Chronotherm IV

  • Page 1 — radiant heat from sun or appliances. — concealed pipes and chimneys. — unheated (uncooled) areas such as an outside wall behind the thermostat. ®U.S. Registered Trademark 69-0936-1 Copyright © 1997 Honeywell Inc. • • All Rights Reserved X-XX UL...
  • Page 2 ® T8611G CHRONOTHERM IV DELUXE PROGRAMMABLE HEAT PUMP THERMOSTATS 5 FEET [1.5 METERS] M10106 Fig. 1. Typical location of thermostat. WALL THERMOSTAT X2 L WIRES THROUGH WALL EQUIPMENT HEAT RELAY RELAY MONITOR 2 WALL COOLING OR EQUIPMENT ANCHORS HEATING CHANGEOVER MONITOR 1 VALVE OUTDOOR...
  • Page 3: Mounting Thermostat

    ® T8611G CHRONOTHERM IV DELUXE PROGRAMMABLE HEAT PUMP THERMOSTATS Using Thermostat Keys The thermostat keys are used to: • set current day and time, • program times and setpoints for heating and cooling, • temporarily override program temperatures, • display present setting, •...
  • Page 4: Installer Setup

    ® T8611G CHRONOTHERM IV DELUXE PROGRAMMABLE HEAT PUMP THERMOSTATS SET WAKE TIMES INCREASE TEMPERATURE AND SETPOINTS SETTING OR SCROLL SET LEAVE TIMES FORWARD THROUGH AND SETPOINTS INCREASE TIME SETTING INSTALLER SETUP OPTIONS OR SCROLL FORWARD THROUGH INSTALLER SET RETURN TIMES SETUP AND SELF-TEST AND SETPOINTS DECREASE TEMPERATURE...
  • Page 5 ® T8611G CHRONOTHERM IV DELUXE PROGRAMMABLE HEAT PUMP THERMOSTATS A combination of key presses are required to use the Installer Setup feature. — To enter the Installer Setup, press and hold the Information i key with the increase decrease keys until the first number is displayed. All display segments appear for approximately three seconds before the number is displayed.
  • Page 6 ® T8611G CHRONOTHERM IV DELUXE PROGRAMMABLE HEAT PUMP THERMOSTATS Table 3. Thermostat Installer Setup Options (Continued). Installer Setup Number (Press Other Choices Time Factory-Setting (Press key to change) key to Actual change) Setting Select Display Description Display Description Extended fan No extended fan Fan operation is extended operation in...
  • Page 7: Setting Current Day And Time

    ® T8611G CHRONOTHERM IV DELUXE PROGRAMMABLE HEAT PUMP THERMOSTATS IMPORTANT INSTALLER SYSTEM-TEST Review the settings to confirm that they match the system. Press Run Program to exit the Use the Installer System-Test to check the thermostat Installer Setup. The thermostat has saved the operation.
  • Page 8: Thermostat Information

    ® T8611G CHRONOTHERM IV DELUXE PROGRAMMABLE HEAT PUMP THERMOSTATS NOTE: Press Time to advance to the next test and Refer to Table 5 for the directions and results of the Time to go back to the previous test. Press specific tests. Run Program to exit the system-test.
  • Page 9: Outdoor Temperature Sensor (Select Models)

    ® T8611G CHRONOTHERM IV DELUXE PROGRAMMABLE HEAT PUMP THERMOSTATS 6. Press the Run Program key to exit the system-test. CHECKOUT The system-test times out after four minutes without any key presses. Outdoor Temperature Sensor (select models) Allow the outdoor temperature sensor to soak in the outdoor air for a minimum of five minutes before taking a reading.
  • Page 10 ® T8611G CHRONOTHERM IV DELUXE PROGRAMMABLE HEAT PUMP THERMOSTATS Troubleshooting (Continued). Symptom Possible Cause Action Cooling will not No power to the thermostat. • Check for 24 Vac between R and C. come on. — If missing 24 Vac: — check if the circuit breaker is tripped—reset the circuit breaker.
  • Page 11 ® T8611G CHRONOTHERM IV DELUXE PROGRAMMABLE HEAT PUMP THERMOSTATS 69-0936—1...
  • Page 12 IV DELUXE PROGRAMMABLE HEAT PUMP THERMOSTATS Helping You Control Your World ® Home and Building Control Home and Building Control Honeywell Inc. Honeywell Limited-Honeywell Limitée Honeywell Plaza 155 Gordon Baker Road P.O. Box 524 North York, Ontario Minneapolis, MN 55408-0524 M2H 3N7 69-0936—1 J.H...