Installer Setup; Installer System Test - Honeywell TH3110DAIRCOMF Installation Manual

Non-programmable digital thermostat
Table of Contents

Advertisement

PRO TH3210D Non-programmable Digital Thermostat

Installer setup

Follow the procedure below to configure the thermostat to match the installed
heating/cooling system, and customize feature operation as desired.
Press and hold both buttons
To begin, press and hold the
buttons until the display changes
Setup Function
6
Auxiliary heat
cycle rate (CPH)
8
Emergency heat
cycle rate (CPH)
9
Compressor
cycle rate (CPH)
14
Temperature
display
15
Compressor
protection

Installer system test

After completing the installer setup above, press the
system test (see next page).
Function
number
and
Settings & Options
5 For gas or oil furnaces of less than 90% efficiency
1 For steam or gravity systems
3 For hot water systems & furnaces of over 90% efficiency
9 For electric furnaces
[Other cycle rate options: 2, 4, 6, 7, 8, 10, 11 or 12 CPH]
9 For electric furnaces
1 For steam or gravity systems
3 For hot water systems & furnaces of over 90% efficiency
5 For gas or oil furnaces of less than 90% efficiency
[Other cycle rate options: 2, 4, 6, 7, 8, 10, 11 or 12 CPH]
3 Recommended for most compressors
[Other cycle rate options: 1, 2, 4, 5 or 6 CPH]
0 Fahrenheit
1 Celsius
5 Five-minute compressor off time
[Other options: 0, 1, 2, 3 or 4-minute off time]
Setting
Setup
6
Press
to change settings
Press
to advance to next function
Press and hold
button again to begin a
7
5
to exit and save settings
**See page 9

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pro th3210dPro th3210d1004