E. Combustible Mantel
•
Refer to the shaded area of Figure 12.6 for the location and dimensions of a combustible mantel.
•
A combustible mantel may be positioned no lower than 22 in. (508 mm) above the top of the fireplace opening.
•
A combustible mantel may have a maximum depth of 12 in. (305 mm).
•
Combustible trim and materials cannot be placed within 6 in. (152mm) of the fireplace opening (top or sides).
•
Combustible materials projecting more than 1 1/2 in. (38 mm) shall not be placed within 12 in. (305 mm) from the top of
the fireplace opening.
•
Combustible trim must not cover the metal surfaces of the fireplace.
Combustible Wall
2 x 4 stud wall
Standoffs
Non-combustible
Decorative Facing
such as:
Steel, iron, brick,
tile, concrete, slate,
glass, plasters.
Seal joint with
non-combustible
sealant
Figure 12.6 Clearances to Mantels or other Combustibles above Fireplace
42
Combustible
Decorative Facing
Metal support to stablize wall and mantel
12 in./305 mm
Mantel
6 in./152 mm
minimum
1 1/2 in./
38 mm
maximum
Measured from top of fireplace opening
Heatilator • Birmingham BIR50-B • 4059-682D • 9/12
7 ft (2134 mm)
base of fireplace
Grid represents
1 in. squares
22 in./559 mm
minimum
12 in./305 mm
minimum
minimum
to ceiling