TYPICAL WIRING SCHEMATIC
ELECTRICAL DATA
58CTA/CTX
VOLTS HERTZ
UNIT SIZE
PHASE
045-08
115-60-1
045-12
115-60-1
070-08
115-60-1
070-12
115-60-1
070-16
115-60-1
090-14
115-60-1
090-16
115-60-1
090-20
115-60-1
110-12
115-60-1
110-16
115-60-1
110-22
115-60-1
135-16
115-60-1
135-22
115-60-1
155-20
115-60-1
* Permissible limits of the voltage range at which unit operates satisfactorily.
† Time--- delay type is recommended.
‡ Length shown is as measured 1 way along wire path between unit and service panel for maximum 2 percent voltage drop.
OPERATING VOLTAGE RANGE
Maximum*
Minimum*
127
104
127
104
127
104
127
104
127
104
127
104
127
104
127
104
127
104
127
104
127
104
127
104
127
104
127
104
MAXIMUM
WIRE
LENGTH --
MAXIMUM
FT (M)‡
UNIT AMPS
5.3
49 (14.9)
7.1
38 (11.5)
5.2
51 (15.5)
7.3
37 (11.2)
10.1
27 (8.2)
8.2
34 (10.3)
9.9
28 (8.5)
12.9
34 (10.3)
8.2
34 (10.3)
10.1
28 (8.5)
13.7
32 (9.7)
10.2
27 (8.2)
14.5
30 (9.1)
15.0
29 (8.8)
14
A95236
MAXIMUM
FUSE OR CKT
MINIMUM
BKR AMPS†
WIRE GAGE
15
14
15
14
15
14
15
14
15
14
15
14
15
14
20
12
15
14
15
14
20
12
15
14
20
12
20
12