Craftsman 580.329120 Owner's Manual page 13

3000 watt ac generator
Hide thumbs Also See for 580.329120:
Table of Contents

Advertisement

Available languages

Available languages

Problem
Correction
Engine is running, but
no AC output is
available.
Engine runs good at
no-load but "bogs
down" when loads
are connected.
Cause
1.
One of the circuit breakers is open.
2.
Fault in generator.
3.
Poor connection or defective cord set.
4.
Connected device is bad.
1.
Short circuit in a connected load.
2.
Engine speed is too slow.
3.
Generator is overloaded.
4.
Shorted generator circuit.
1.
Run/Stop Switch set to "STOP".
2.
Dirty air cleaner.
3.
Out of gasoline.
4.
Stale gasoline.
5.
Spark plug wire not connected to
1.
Reset circuit breaker.
2.
Contact Sears service facility.
3.
Check and repair.
4.
Connect another device that is in
good condition.
1.
Disconnect shorted electrical load.
2.
Contact Sears service facility.
3.
See "Don't Overload the
Generator" on page 9.
4.
Contact Sears service facility.
1.
Set switch to "RUN".
2.
Clean or replace air cleaner.
3.
Fill fuel tank.
4.
Drain gas tank and carburetor; fill
with fresh fuel.
5.
Connect wire to spark plug.
Engine will not start;
or starts and runs
rough.
spark plug.
6.
Bad spark plug.
7.
Water in gasoline.
8.
Overprimed or flooded.
9.
Excessively rich fuel mixture.
6.
Replace spark plug.
7.
Drain gas tank and carburetor; fill
with fresh fuel.
8.
Wait 5 minutes and re-crank
engine.
9.
Contact Sears service facility.
Engine shuts down
when runninq.
Engine lacks power.
Engine "hunts"
or
falters.
10. Intake valve stuck open or closed.
11. Engine has lost compression.
1.
Out of gasoline.
1.
Load is too high.
2.
Dirty air filter.
Carburetor is running too rich or too lean.
10. Contact Sears service facility.
11. Contact Sears service facility.
1.
Fill fuel tank.
1.
See "Don't Overload the Generator"
on page 9.
2.
Replace air filter.
Contact Sears service facility.