Venting: Direct Vent System (Flex) - Excalibur P95-NG2 Owners & Installation Manual

P95-2 zero clearance direct vent gas fireplace
Table of Contents

Advertisement

INSTALLATION
These venting systems, in combination with the P95-2 Direct Vent Gas Fireplace, have been tested and listed as a direct vent heater system by
Warnock Hersey. The location of the termination cap must conform to the requirements in the Vent Terminal Locations diagram on page 11.
FPI Direct Vent (Flex) System Termination
Kit (Part # 946-615) includes all the parts
needed to install the P95-2 with a maxi-
mum run of 4 feet.
1) 8" dia. flexible liner (4 ft. length)
2) 5" dia. flexible liner (4 ft. length)
3) spring spacers (4)
4) thimble (2)
5) AstroCap XL termination cap (1)
6) screws (12)
7) tube of Mill Pac (1)
8) plated screws (8)
9) screws #8 x 1-1/2" Drill Point, Stainless
Steel (4)
10) vinyl siding standoff
10
FPI Direct Vent System (Flex) Horizontal Terminations Only
If longer runs are needed, the FPI Direct
Vent system (Flex) kit is (Part # 946-616)
which includes all the parts needed to
install the P95-2 with a maximum 10' run.
1) 8" dia. flexible liner (10 ft. length)
2) 5" dia. flexible liner (10 ft. length)
3) spring spacers (7)
4) thimble (2)
5) AstroCap XL termination cap (1)
6) screws (12)
7) tube of Mill Pac (1)
8) plated screws (8)
9) screws #8 x 1-1/2" Drill Point, Stainless
Steel (4)
10) vinyl siding standoff
VENTING
Excalibur P95-2 Zero Clearance Direct Vent Gas Fireplace
Notes:
1) Liner sections should be continuous
without any joints or seams.
2) Only Flex pipe purchased from FPI
may be used for Flex installations.
3) Horizontal vent must be supported
every 3 feet.