Facility Power Requirements And Characteristics - Fujitsu SPARC Enterprise M3000 Installation Manual

Hide thumbs Also See for SPARC Enterprise M3000:
Table of Contents

Advertisement

TABLE 2-3
Item
Number of power cables
Power cord length
Redundancy
Input voltage
*
Rated current
Frequency
Power consumption (maximum)
Apparent power
Heat dissipation
Power factor
* In a redundant configuration, the rated current per cable is half the value shown in
TABLE 2-4
Destination
Japan
North America
China
Hong Kong
South Korea
2.2.2.2

Facility Power Requirements and Characteristics

For proper redundancy, the facility must have two independent power sources. That
is, circuit breakers must be connected either to separate power company utility feeds
or to an uninterruptible power system (UPS). For power redundancy, the power
cables must not be connected to the same facility power source.
Electrical Specifications
Specification
100 to 120 VAC
2 (1 cable for each power supply unit)
3 m/9.84 ft
1 + 1 redundant configuration
100 to 120 VAC
4.80 A
50/60 Hz
470 W
480VA
1,603.7 BTU/hr (1,692 KJ/hr)
0.98 (full configuration)
Power Cords and Connector Shape
200 to 240 VAC
200 to 240 VAC
2.59A
460W
517VA
1,569.6 BTU/hr (1,656 KJ/hr)
0.89 (full configuration)
TABLE 2-3
Power cable type
NEMA 5-15 125V15A
NEMA L6-15 250V15A
GB 2099.1
250V15A
IEC60320-C14
250V15A
IEC 60320-C14
250V15A
Chapter 2
Preparing to Install the Server
.
Connector shape
IEC 60320 C13
2-5