Maintenance - Carrier 30XA080-500 Controls, Start-Up, Operation, Service And Troubleshooting Instructions

Air-cooled liquid chillers
Table of Contents

Advertisement

Charging
with Unit Off and Evacuated
--
Close liquid line
service valve before charging. Weigh in charge shown on unit
nameplate.
Open liquid line service valve; start unit and allow
it to run several minutes fully loaded. Check for a clear sight
glass. Be sure clear condition
is liquid and not vapoc
Charging
with Unit Running
-- If charge is to be added while
unit is operating,
all condenser
fans and compressol_
must be
operating. It may be necessa U to block condenser
coils at low
ambient temperatures
to raise condensing
pressure to approxi-
mately 198 psig (1365 kPa) to turn all condenser
fans on. Do not
totally block a coil to do this. Partially block all coils in unif(mn
pattern. Chtu_ge each circuit until sight glass shows dear liquid,
and has a liquid line temperature
of 103 F (39 C) for 30XA080-
350 units and 108 F (42 C) for 30XA400-500
units.
Add 5 lb (2.3 kg) of liquid chtu_ge into the entering
filter
drier using the fitting located on the tube entering the bottom of
the coolec This fitting is located between the electronic
expan-
sion valve (EXV) and the coolel:
Allow the system to stabilize trod then recheck the liquid
temperature.
If needed,
add additional
liquid charge,
5 lb
(Z3 kg) at a time, allowing
the system to stabilize between
each charge
addition.
Slowly add charge
as the sight glass
begins to clear to avoid overcharging.
IMPORTANT:
When adjusting refrigerant chtuge, circu-
late fluid through cooler continuously
to prevent freezing
and possible dmnage to the coolel: Do not overcharge,
and
never charge liquid into the low-pressure
side of system.
Safety DeviceS--The
30XA
chillers
cont;fin
many
safety devices
and protection
logic built into the electronic
control Following
is a description
of the major safeties.
COMPRESSOR
PROTECTION
Motor Overload
--
The
compressor
protection
modules
(CPM)
protect each compressor
against overcurrent.
Do not
bypass the current
transducel_
or make any changes
to the
factory-installed
and configured
headers. The configuration
of
these headers defines the Must Trip Amps (MTA) at which the
CPM will turn the compressors
off. Determine
the c;mse for
trouble and correct the problem before resetting the CPM. See
Appendix
C for MTA settings and configuration
headers.
Each CPM bo;ud also reads the status of each compressor's
high-pressure
switch. All compressors
have factory-installed
high-pressure
switches. See Table 37.
Table 37 --
High-pressure
Switch
Settings
SWITCH SETTING
UNIT
psig
]
kPa
30XA
304.5
_+14.5
2099
_+100
If the switch opens during operation,
the compressor
will be
shut down. The CPM will reset automatic_flly when the switch
closes, however,
a manual
reset of the control is required to
restart the compressor:
OIL SEPARATOR
HEATERS
-- Each
oil separator
circuit
has a heater mounted on the underside
of the vessel. The heater
is deenergized
anytime the compressor
is on. If the compressor
is off and outdoor-air
temperature
(OAT) is greater than 100 F
(37.8 C) the heater
is deenergized.
The heater
will also be
deenergized
if OAT - SST >32 F (17.8 ° C) and the OAT -
LWT
> 32F (17.8° C).
COOLER
PROTECTION
Low Water Temperature
--
Microprocessor
is programmed
to shut the chiller down if the leaving fluid temperature
drops
below 34 F (1.1 C) for water or more than 8 ° F (4.4 ° C) below
set point for Fluid Type = brine. When the fluid temperature
rises 6 ° F (3.3 ° C) above the leaving fluid set point, the safety
resets and the chiller restarts. Reset is automatic
as long as this
is the first occurrence
of the day.
IMPORTANT:
If unit is installed
in an area where
ambient
temperatures
fall below
32 F (0 ° C), a suit-
able corrosion-inhibited
antifreeze
solution
or cooler
heater must be used in the chilled water circuit.
Relief Devices
--
Fusible
plugs are located in each cir-
cuit between the condenser
and the liquid line shutoff valve.
PRESSURE
RELIEF VALVES -- Valves ;ue installed in each
circuit
and
are located
on all coolers.
These
valves
are
designed
to relieve if an abnormal
pressure condition
_uises.
Relief
valves
on _fll coolers
lelieve
at 220 psi (1517 kPa).
These
valves
should
not be capped.
If a valve lelieves,
it
should be replaced. If the valve is not replaced, it may relieve
at a lower pressure, or leak due to trapped dirt from the system
which may prevent resealing.
Plessure relief valves located on cooler shells have 3/4-in.
NPT connections
for lelief. Some local building codes require
that relieved
gases be exhausted
to a specific location.
This
connection
_fllows conformance
to this requirement.
MAINTENANCE
Recommended
Maintenance
Schedule -- The fol-
lowing
are only recolmnended
guidelines.
Jobsite conditions
may dictate that maintenance
schedule is performed more often
than recommended.
Routine:
For machines
with E-coat condenser
coils:
Check condenser
coils for debris; clean as necessary
with
Carrier approved
coil cleaner.
Periodic
clean
water
rinse,
especially
in coastal
and
industrial
applications.
Every month:
Check condenser
coils for debris; clean as necessary
with
Carrier approved
coil cleaner.
Check moisture
indicating
sight glass for possible
refrig-
erant loss and presence
of moisture.
Every 3 months (for all machines):
Check refrigerant
charge.
Check
all refrigerant
joints
and
valves
for refrigerant
leaks; repair as necessary.
Check chilled water flow switch operation.
Check all condenser
fans for proper operation.
Check oil filter pressure
drop.
Check oil separator
heater operation.
Every 12 months (for all machines):
Check all electrical
connections;
tighten as necessary.
Inspect all contactors
and relays; replace
as necessary.
Check
accuracy
of thermistors;
replace
if greater
than
_+2 ° F (1.2 ° C) variance
fiom calibrated
thermometer.
Check
accuracy
of transducers;
replace
if greater
than
_+5psi (34.47 kPa) variance.
Check
to be sure that the proper
concentration
of anti-
freeze is present in the chilled water loop, if applicable.
Verify that the chilled water loop is properly
treated.
Check
refrigerant
filter
driers
for excessive
pressure
drop; replace
as necessary.
Check chilled water strainers,
clean as necessary.
Check cooler heater operation.
Check
condition
of condenser
fan blades
and that they
are securely fastened
to the motor shaft.
Perform Service Test to confirln operation of all components.
Check
for excessive
cooler
approach
(Leaving
Chilled
Water Temperature - Saturated Suction Temperature)
which
may indicate fouling. Clean cooler vessel if necessary.
Obtain oil analysis; change as necessmy.
TROUBLESHOOTING
See Table 38 for an abbreviated
list of sylllptolllS, possible
causes and possible remedies.
66

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents