Charging
with Unit Off and Evacuated
--
Close liquid line
service valve before charging. Weigh in charge shown on unit
nameplate.
Open liquid line service valve; start unit and allow
it to run several minutes fully loaded. Check for a clear sight
glass. Be sure clear condition
is liquid and not vapoc
Charging
with Unit Running
-- If charge is to be added while
unit is operating,
all condenser
fans and compressol_
must be
operating. It may be necessa U to block condenser
coils at low
ambient temperatures
to raise condensing
pressure to approxi-
mately 198 psig (1365 kPa) to turn all condenser
fans on. Do not
totally block a coil to do this. Partially block all coils in unif(mn
pattern. Chtu_ge each circuit until sight glass shows dear liquid,
and has a liquid line temperature
of 103 F (39 C) for 30XA080-
350 units and 108 F (42 C) for 30XA400-500
units.
Add 5 lb (2.3 kg) of liquid chtu_ge into the entering
filter
drier using the fitting located on the tube entering the bottom of
the coolec This fitting is located between the electronic
expan-
sion valve (EXV) and the coolel:
Allow the system to stabilize trod then recheck the liquid
temperature.
If needed,
add additional
liquid charge,
5 lb
(Z3 kg) at a time, allowing
the system to stabilize between
each charge
addition.
Slowly add charge
as the sight glass
begins to clear to avoid overcharging.
IMPORTANT:
When adjusting refrigerant chtuge, circu-
late fluid through cooler continuously
to prevent freezing
and possible dmnage to the coolel: Do not overcharge,
and
never charge liquid into the low-pressure
side of system.
Safety DeviceS--The
30XA
chillers
cont;fin
many
safety devices
and protection
logic built into the electronic
control Following
is a description
of the major safeties.
COMPRESSOR
PROTECTION
Motor Overload
--
The
compressor
protection
modules
(CPM)
protect each compressor
against overcurrent.
Do not
bypass the current
transducel_
or make any changes
to the
factory-installed
and configured
headers. The configuration
of
these headers defines the Must Trip Amps (MTA) at which the
CPM will turn the compressors
off. Determine
the c;mse for
trouble and correct the problem before resetting the CPM. See
Appendix
C for MTA settings and configuration
headers.
Each CPM bo;ud also reads the status of each compressor's
high-pressure
switch. All compressors
have factory-installed
high-pressure
switches. See Table 37.
Table 37 --
High-pressure
Switch
Settings
SWITCH SETTING
UNIT
psig
]
kPa
30XA
304.5
_+14.5
2099
_+100
If the switch opens during operation,
the compressor
will be
shut down. The CPM will reset automatic_flly when the switch
closes, however,
a manual
reset of the control is required to
restart the compressor:
OIL SEPARATOR
HEATERS
-- Each
oil separator
circuit
has a heater mounted on the underside
of the vessel. The heater
is deenergized
anytime the compressor
is on. If the compressor
is off and outdoor-air
temperature
(OAT) is greater than 100 F
(37.8 C) the heater
is deenergized.
The heater
will also be
deenergized
if OAT - SST >32 F (17.8 ° C) and the OAT -
LWT
> 32F (17.8° C).
COOLER
PROTECTION
Low Water Temperature
--
Microprocessor
is programmed
to shut the chiller down if the leaving fluid temperature
drops
below 34 F (1.1 C) for water or more than 8 ° F (4.4 ° C) below
set point for Fluid Type = brine. When the fluid temperature
rises 6 ° F (3.3 ° C) above the leaving fluid set point, the safety
resets and the chiller restarts. Reset is automatic
as long as this
is the first occurrence
of the day.
IMPORTANT:
If unit is installed
in an area where
ambient
temperatures
fall below
32 F (0 ° C), a suit-
able corrosion-inhibited
antifreeze
solution
or cooler
heater must be used in the chilled water circuit.
Relief Devices
--
Fusible
plugs are located in each cir-
cuit between the condenser
and the liquid line shutoff valve.
PRESSURE
RELIEF VALVES -- Valves ;ue installed in each
circuit
and
are located
on all coolers.
These
valves
are
designed
to relieve if an abnormal
pressure condition
_uises.
Relief
valves
on _fll coolers
lelieve
at 220 psi (1517 kPa).
These
valves
should
not be capped.
If a valve lelieves,
it
should be replaced. If the valve is not replaced, it may relieve
at a lower pressure, or leak due to trapped dirt from the system
which may prevent resealing.
Plessure relief valves located on cooler shells have 3/4-in.
NPT connections
for lelief. Some local building codes require
that relieved
gases be exhausted
to a specific location.
This
connection
_fllows conformance
to this requirement.
MAINTENANCE
Recommended
Maintenance
Schedule -- The fol-
lowing
are only recolmnended
guidelines.
Jobsite conditions
may dictate that maintenance
schedule is performed more often
than recommended.
Routine:
For machines
with E-coat condenser
coils:
•
Check condenser
coils for debris; clean as necessary
with
Carrier approved
coil cleaner.
•
Periodic
clean
water
rinse,
especially
in coastal
and
industrial
applications.
Every month:
•
Check condenser
coils for debris; clean as necessary
with
Carrier approved
coil cleaner.
•
Check moisture
indicating
sight glass for possible
refrig-
erant loss and presence
of moisture.
Every 3 months (for all machines):
•
Check refrigerant
charge.
•
Check
all refrigerant
joints
and
valves
for refrigerant
leaks; repair as necessary.
•
Check chilled water flow switch operation.
•
Check all condenser
fans for proper operation.
•
Check oil filter pressure
drop.
•
Check oil separator
heater operation.
Every 12 months (for all machines):
•
Check all electrical
connections;
tighten as necessary.
•
Inspect all contactors
and relays; replace
as necessary.
•
Check
accuracy
of thermistors;
replace
if greater
than
_+2 ° F (1.2 ° C) variance
fiom calibrated
thermometer.
•
Check
accuracy
of transducers;
replace
if greater
than
_+5psi (34.47 kPa) variance.
•
Check
to be sure that the proper
concentration
of anti-
freeze is present in the chilled water loop, if applicable.
•
Verify that the chilled water loop is properly
treated.
•
Check
refrigerant
filter
driers
for excessive
pressure
drop; replace
as necessary.
•
Check chilled water strainers,
clean as necessary.
•
Check cooler heater operation.
•
Check
condition
of condenser
fan blades
and that they
are securely fastened
to the motor shaft.
•
Perform Service Test to confirln operation of all components.
•
Check
for excessive
cooler
approach
(Leaving
Chilled
Water Temperature - Saturated Suction Temperature)
which
may indicate fouling. Clean cooler vessel if necessary.
•
Obtain oil analysis; change as necessmy.
TROUBLESHOOTING
See Table 38 for an abbreviated
list of sylllptolllS, possible
causes and possible remedies.
66