Dual Switch; Ice Mode - Carrier 30XA080-500 Controls, Start-Up, Operation, Service And Troubleshooting Instructions

Air-cooled liquid chillers
Table of Contents

Advertisement

Table 19 -- Control Methods and Cooling Set Points
PARAMETER
Heat Cool
Ice Mode
Control Method
Select
Setpoint Select
Enable
( OPER)
(HC.SE)
(SP.SE)
(ICE.M)
Enable
0
(Switch Ctrl)
1
(Time Sched)
2
(CCN)
-- = No Effect
o
(Cool)
o
(Cool)
0
(Cool)
1
(Setpointl)
2
(Setpoint2)
3
(4-20mA Setp)
4
(Dual Setp Sw)
0
(Setpoint Occ)
Enable
Enable
Enable
Enable
Enable
Ice Done
UCE.D)
Open
Open
Open
Closed
Open
Closed
Open
Closed
Open
Dual Setpoint
Switch (DUAL)
Closed
Closed
Open
Closed
Closed
Open
Closed
Closed
Closed
m
m
m
m
m
Setpoint
Occupied (SP.OC)
Occupied
Unoccupied
Unoccupied
Occupied
Unoccupied
Unoccupied
SET
POINT
CSP.1
CSP.3
CSP.2
CSP.3
4-20 mA
CSP.1
CSP.3
CSP.2
CSR 1
CSP.2
CSP.3
CSP.2
CSR 1
C$P.2
CSP.3
CSP.2
CSP.1
CSP.2
CSR 3
UNIT RUN STATUS (Run Status--+VIEW_STAT)-
As the
unit transitions
from off to on and back to off. the Unit Run
Status will change based on the unit's operational
status. The
variables ree: 0 (Oft), 1 (Running),
2 (Stopping),
and 3 (Delay).
0 indicates
the unit is Off due to the Enable/Off/Remote
Contact Switch,
a time schedule
or CCN command.
1 indicates
the unit is operational.
2 indicates
the unit is shutting
down due to the command
to
shut
down
fiom
the
Enable/Off/Remote
Contact
Switch,
a time schedule
or CCN command.
3 indicates
the unit has received
a command
to start fiom
Enable/Off/Remote
Contact
Switch,
a time schedule
or
CCN
command,
and is waiting
for the start-up
timer
(Configuration
_OPTN--+DELY)
to expire.
Cooling
Set
Point
Selection
(Operating
Modes
_SLCT_SP.SE)-
Several
options
for controlling
the
Leaving Chilled Water Set Point are offered and are configured
by the Cooling Set Point Select vmiables.
[n addition
to the
Cooling
Set Point Select,
Ice Mode Enable
(Configuration
--OPTN---)ICE.M),
and
Heat
Cool
Select
(Operating
Modes---) SLCT---)HCSE)
vmiables also have a role in deter-
mining the set point of the machine. All units are shipped from
the factory with the Heat Cool Select variable set to HC.SE=O
(Cooling).
All set points me based on Leaving
Water Control,
(Configuration
---)SER V---)EWTO=NO
).
In ;dl cases, there are limits on what values are allowed for
each set point. These values depend on the Cooler Fluid Type
(Cot_guration--_SERV--+FLUD)
and the Brine Freeze
Set
point (Cot_guration
--+SERV--+LOSP).
See Table 20.
Table 20 -- Configuration Set Point Limits
SET POINT LIMIT
Minimum*
Maximum
COOLER FLUID TYPE, FLUD
1 =Water
]
2 = Medium Brine
38 F (3.3 C)
I
14 F (-10.0 C)
60 F (15.5 C)
*The minimum set point for Medium Temperature
Brine applications
is related to the Brine Freeze Point. The set point is limited to be no
less than the Brine Freeze Point +5 ° F (2.8 ° C). See Table 19.
SET
PO[NT
1 (Operating
Modes--_LCT-+SP.SE=I)
--
When
Set Point Select
is configured
to 1, the unit's active
set point
is based
on Cooling
Set
Point
1 (Set Point
_'OOL
_CSP. 1).
SET
POINT
2 (Operating
Modes--_S'LCT-+SP.SE=2)
--
When
Set Point Select
is configured
to 2, the unit's active
set point
is based
on Cooling
Set
Point
2 (Set Point
_4JOOL
_CSP.2).
4
TO
20
mA
INPUT
(Operating
Modes--+SLCT
---)SP.SE=3) -- When Set Point Select is configured
to 3, the
unit's active set point is based on an external 4 to 20 mA signal
input to the Energy Management
Module (EMM).
See Table 19 for Control Methods
and Cooling Set Points.
The following
equation
is used to control the set point. See
Fig. 15.
Set Point = 10 + 70(mA - 4)/16 (deg F)
Set Point = - 12.2 + 38.9(mA - 4)/16 (deg C)
DUAL
SWITCH
(Operating
Modes--)SLCT--_S'P.SE=4)
--
When Set Point Select is configured
to 4, the unit's active set
point is based on Cooling
Set Point 1 (Set Point_COOL-e
CSP.I) when the Dual Set Point switch contacts
me open and
Cooling Set Point 2 (Set Point_ZJOOL_ZJSP.2)
when they
are closed.
ICE MODE
--
Operation
of the machine to make and store
ice can be accomplished
many ways. The Energy Management
Module and an [ce Done Switch is requiled
for operation in the
Ice Mode. [n this configuration,
the machine
can operate with
up to three cooling set points: Cooling Set Point 1 (Occupied)
(Set Point_COOL_CSP.I),
Cooling
Set Point 2 (Unoccu-
pied)
(Set
Point_COOL_CSP.2),
and
Ice
Set
Point
(Set Point _COOL
_CSP.3).
SET
PO[NT
OCCUPANCY
(Operating
Modes
SLCT-+SP.SE=O)
-- When Set point Select is configured
to
0, the unit's active set point is based on Cooling Set Point 1
(Set Point_'OOL
_CSP.I)
during the occupied period while
operating
under
Time
Cloek-+SCHI.
ff the Time
Clock
-eSCH2
is in use, the unit's
active
set point
is based
on
Cooling
Set
Point
1 (Set Point_COOL_CSP.I)
during
the occupied
period
and
Cooling
Set Point
2 (Set Pohlt
_4JOOL
_CSP.2)
during the unoccupied
period.
3O