Fan Boards
--
At least one f;m board is installed in each
unit. See Fig. 5A and 5B. There are two types of fan bomds,
with and without an analog output signal for the low ambient
temperature
head pressure
control fan speed controllers.
If a
unit does not have low ambient temperature
head pressure con-
trol installed, it will not have the analog connection
terminals.
The fan bo;ud responds to commands
from the MBB and sends
the MBB the results of the channels
it monitors
via the Local
Equipment
Network
(LEN). See below for fan board A, B and
C DIP switch addresses. See Tables 7-9 for inputs and outputs.
FAN BOARD
(080)
1
2
3
4
5
6
7
8
DIP SWITCH
Address:
OFF
ON
OFF
OFF
ON
OFF
ON
OFF
FAN BOARD A
(090-500)
1
2
DIP SWITCH
Address:
OFF
ON
3
4
5
6
7
8
OFF
OFF
ON
OFF
ON
OFF
FAN BOARD B
(140-500)
1
2
DIP SWITCH
Address:
ON
ON
3
4
5
6
7
8
OFF
OFF
ON
OFF
ON
OFF
FAN BOARD C
(400-500)
1
2
DIP SWITCH
Address:
OFF
OFF
3
4
5
6
7
8
ON
OFF
ON
OFF
ON
OFF
LOCATION OF
DIP SWITCH
JSERIALNUMBER
/
IIIIIIIIIIIII IIIIIIIIIIIIIIIIIIIIIII . ../7
_
_]TATUS
SIC (LE_
_
_..
IgN3NNl1345
_
_
[__
[_JFr_d@)
c
_
C
TB1
TB2
TB3
TB4
TB5
TB6
TB7
TB8
J2
I/I
I_
I+-
Fig. 5A-
Fan Board (AUX 1)with Low Ambient Temperature
Head Pressure Control
LOCATION OF
DIP SWITCH
cccccc Q
TB1
TB2
TB3
TB4
TB5
TB6
TB7
TB8
/ cn_I cn_ I CH_ I CH4I/ CHa I CH_ I CHV I CHS I
Fig. 5B -- Fan Board (AUX 2) without
Low Ambient
Temperature
Head Pressure
Control
11

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents