OPERATION
Section 3 - Operation
Air-cooled Generators
-A A.
/_
Do not attempt
to activate
the transfer
switch
manually
until all power voltage supplies to the
switch have been positively turned
off. Failure
to turn off all power voltage supplies may result
in extremely
hazardous
and possibly fatal elec-
trical shock.
5.
Use the manual
transfer
handle
inside
the trans-
fer switch
to move the main contacts
back to their
UTILITY position,
i.e., loads
connected
to the util-
ity power
source
(Figure
3.2).
6.
Turn
ON the utility
power
supply
to the transfer
switch
using
the means
provided.
7.
Set the system
to automatic
operation
as outlined
in Automatic
Transfer
Operation
section.
3.5
SIDE COMPARTMENT (V-TWIN
ONLY) (nCURES 3.4&3.s)
Local
codes
may
require
this
compartment
to
be
locked.
A hasp
is provided
so the
owner
can
secure
the
compartment
with
their
own
padlock.
Check
local
codes
in the area.
____,3_..1 MAiN
IR
IT BREAKER
This
is
a
2-pole
breaker
rated
according
to
the
Specifications
section.
EXTERIOR READY LI NT
. Green
LED 'Ready'
light (10, 12, 14, 16, 17 & 20
KW) is on when
utility
is present
and switch
is in
AUTO indicating
the generator
is ready
and when
the generator
is running.
. Red LED
7klarm'
light
(10,
12, 14, 16,
17 & 20
KW) is on when
the generator
is OFF or a fault is
detected.
(See the Protections
Systems
section.)
. Yellow LED 'Maintenance'
light (17 & 20 KW) (See
the Protections
Systems
section.)
@ 3.5.3
120 VAC GFCI OUTLET & 15 AMP
BREAKER (17 & 20 KW ONLY)
These
models
are equipped
with
an external,
15 amp,
120
volt,
GFCI
convenience
outlet
that
is located
in
a compartment
on the right
side
of generator
(Figure
1.3).
When
the generator
is running,
in the absence
of util-
ity power,
this
outlet
may also
be used
to power
items
outside
your
home
such
as lights
or power
tools.
This
outlet
may
also
be
used
when
utility
power
is pres-
ent by running
the
generator
in manual
mode.
This
outlet
does
not
provide
power
if the generator
is not
running.
This
outlet
is protected
by a 15 amp
circuit
breaker
in the
same
compartment
as the
outlet.
(Do
not
use
when
the
generator
is running
in exercise
mode.)
2o
Figure
3.4 - Side Compartment
Figure
3.5-
Open Side Compartment
_.o_. _o_ 120
V GECL0utlet_.
3.6
PROTECTION SYSTEMS
ALARM_
Highest
Priority
{Latching)
Displayed
on the
con-
trol
panel
and
the
external
red
LED
(V-twins
only).
They
must
be cleared
before
the alarm
message
goes
away.
The
alarm
log
records
each
occurrence
(see
Appendix
- "Menu
System").
+
Low Oil Pressure (Shutdown
Alarm)
A five (5) second
delay
on start-up
and
seven
(7) sec-
ond
delay
once
the
engine
is running.
This
switch
(Figure
3.6)
has
normally
closed
con-
tacts
that
are
held
open
by engine
oil pressure
dur-
ing
operation.
Should
the
oil
pressure
drop
below
the five
(5) PSI
range,
switch
contacts
close
and
the
engine
shuts
down.
The
unit
should
not be restarted
until
oil level
is verified.