Specifications; Generator; Engine; Protection Systems - Generac Power Systems 20 kW Synergy Owner's Manual

60 hz air-cooled generators
Table of Contents

Advertisement

Specifications

Generator

Model
Rated Voltage
Rated Maximum Load Current
(Amps) at rated voltage (LP)*
Main Circuit Breaker
Phase
Rated AC Frequency
Battery Requirement
Enclosure
Unit Weight (lbs/kilos)
Normal Operating Range
These generators are rated in accordance with UL 2200, Safety Stan-
dard for Stationary Engine Generator Assemblies, and CSA-C22.2 No.
100-04 Standard for Motors and Generators.
* Natural Gas ratings will depend on specific fuel joules/BTU content.
Typical derates are between 10-20% off the LP gas rating.
** Circuits to be moved must be protected by same size breaker. For
example, a 15 amp circuit in the main panel must be a 15 amp circuit
in the transfer switch.
Owner's Manual for 60 Hz Synergy™ Generators
20 kW Synergy
240
83.3
100 Amp
1
60 Hz
12 volts, Group 26R-540CCA
Minimum or Group 35AGM-
650CCA Minimum
Replacement Parts
(see
Aluminum
481 / 218
This unit is tested in accordance to
UL 2200 standards with an operat-
ing temperature of -20 ºF (-29 ºC)
to 122 ºF (50 ºC). For areas where
temperatures fall below 32 ºF (0
ºC), cold weather accessories are
recommended. When operated
above 77 ºF (25 ºC) there may be a
decrease in engine power. (Please
reference the engine specifica-
tions.)

Engine

Model
Type of Engine
Number of Cylinders
Displacement
Cylinder Block
Recommended Spark Plug
Spark Plug Gap
Valve Clearance
)
Starter
Oil Capacity Including Filter
Recommended Oil Filter
Recommended Air Filter
Engine power is subject to and limited by such factors as fuel BTU/joules,
ambient temperature and altitude. Engine power decreases about 3.5
percent for each 1000 feet (304.8 meters) above sea level and also will
decrease about 1 percent for each 6 ºC (10 ºF) above 15 ºC (60 ºF) ambi-
ent temperature.
The specification sheet for your generator was included
in the documentation provided with the unit at the time of
purchase. For additional copies, consult your local
Independent Authorized Service Dealer (IASD) for your
specific generator model.

Protection Systems

The generator may need to run for long periods of time
with no operator present to monitor the engine/generator
conditions. The generator is equipped with protection
systems to automatically shut down the unit to protect
against potentially damaging conditions. Some of these
systems include:
Alarms:
High Temperature
Low Oil Pressure
Overcrank
Overspeed
Overvoltage
Undervoltage
Overload
General Information
20 kW Synergy
G-Force 1000 Series
2
999 cc
Aluminum w/ cast iron sleeve
see
Replacement Parts
1.02 mm (0.040 in)
0.05 - 0.1 mm
(0.002 - 0.004 in)
12 VDC
Approx. 1.9 qt (1.8 L)
see
Replacement Parts
see
Replacement Parts
Underspeed
RPM Sensor Loss
Controller Fault
Wiring Error
Fuse Problem
Stepper Overcurrent
7