Field Charging - EMI Corp Manual

Emi corp. emi america series multi-zone heat pump condensing units
Table of Contents

Advertisement

REFRIGERANT PIPING INSTALLATION SECTION
CIRCUIT
EVAPORATOR
CAPACITY
WLHA09, CAHB12
9,000 Btuh
WLHA12, CAHB12
12,000 Btuh
1. To find the charge adjustment and system charge for any evaporator and tubing length:
Line Adjustment = (Line Charge/FT) x Line Length
System Total = Factory Charge + Line Adjustment
2. Round to the nearest ounce and allow for gauges and hoses.
The use of the superheat method is highly
recommended for field charging or checking
the existing refrigerant charge in a system.
Because each installation is different in terms
of indoor air flow, refrigerant line length, etc..,
the factory charge may not be correct for
every application. To assure the best perfor-
mance from the air-conditioner, the refrigerant
charge should be checked and adjusted, if
need be, on each installation.
For proper superheat readings, a standard
low-side refrigerant gauge and an accurate
thermometer are needed. A mercury or
stem-type thermometer is not adequate
for suction-line temperatures. We recom-
mend electric thermocouple thermometers
(available at most refrigeration wholesal-
Multi-zone Heat Pump Condensing Units
REFRIGERANT CHARGE TABLE FOR S2HA
PAIRING
CHG/FT
.25 OZ.
WLHA12
.25 OZ.
CAHB12
IMPORTANT NOTES:

FIELD CHARGING

LINE
LINE
LENGTH
10
25
50
10
25
50
ers); however an accurate remote-bulb
thermometer can be used. When mea-
suring the line temperature, be sure the
thermometer is well insulated to assure
accurate measurements. The chart below
gives superheat values at various outdoor
temperatures. Allow at least 5 minutes run-
ning time between charge adjustments for
the unit to stabilize.
The S2HA has manifold access points on
each of the service valves for the high and
low pressures in cooling mode. There is an
additional "common suction" access point
above each service valve set to provide
low pressure access in the heating mode
as both service valves are at high side
pressure.
11
FACTORY
LINE
CHARGE
ADJUST
S2HA
3 OZ.
6 OZ.
42
13 OZ.
3 OZ.
6 OZ.
46
13 OZ.
www.enviromaster.com
SYSTEM
TOTAL
S2HA
45
48
55
49
52
59