Loading Connections; Adjustment; Type 1051 And 1052 Turnbuckle Adjustment - Emerson 1051 Instruction Manual

Sizes 40, 60 and 70 styles h and j rotary actuators
Hide thumbs Also See for 1051:
Table of Contents

Advertisement

Instruction Manual
Form 5587
November 2006
Center of Gravity Dimensions
ACTUATOR
ACTUATOR
ACTUATOR
ACTUATOR
TYPE
SIZE
40
1051
1051
60
40
60
1052
1052
70
Figure 9. Center of Gravity Dimensions
Loading Connection
1. Connect the loading pressure piping to the
pressure connection in the top of the diaphragm
casing.
For size 40 through 60 actuators, run either 1/4-inch
pipe or 3/8-inch tubing between the 1/4-inch
pressure connection and the positioner or automatic
controller.
For size 70 actuators, run either pipe or tubing
between the pressure connection and the positioner
or automatic controller. If necessary, remove
the 1/4-inch bushing in the pressure connection to
increase connection size.
2. Keep the length of pipe or tubing as short as
possible to avoid transmission lag in the control
signal. If an accessory (such as a volume booster or
a positioner) is used, be sure that the accessory is
properly connected to the actuator. If a positioner is
X
Y
mm
Inch
mm
15
0.6
191
10
0.4
361
15
0.6
241
10
0.4
432
23
0.9
488
part of the assembly, the pressure connection to the
actuator will normally be made at the factory.
Inch
3. When the actuator is completely installed and
7.5
connected to the instrument, check for correct action
14.2
(air-to-open or air-to-close) to match the controlling
9.5
instrument. For successful operation, the actuator
17.0
stem and operating shaft must move freely in
19.2
response to the loading pressure change on the
diaphragm.

Adjustment

Before performing any adjustment
steps, follow the steps in the
WARNING at the beginning of the
Maintenance section.
Type 1051 and 1052 Turnbuckle
Adjustment
Correct turnbuckle adjustment ensures that the valve
body or other operated equipment is correctly closed
when the actuator is against its travel stops. The
turnbuckle adjustment is the only adjustment
necessary on the Type 1051 actuator. Key numbers
used in this procedure are shown in figure 12 for
Type 1051 actuators and in figure 13 for Type 1052
actuators.
For accurate adjustment, remove the valve body or
other operated equipment from the pipeline.
A regulated air supply will be required to stroke the
actuator. Consult table 9 for the sizes of the three
open end wrenches required for this procedure.
1. Remove the access plate (key 59). Also remove
the machine screws (key 60), if present.
For the most accurate adjustment of
the actuator, do not remove the cover
(key 33) during this procedure.
2. Loosen the lower locknut (key 16).
1051 & 1052 H & J
WARNING
Note
11

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

10521051 j1051 h1052 j1052 hFisher 1051 ... Show all

Table of Contents