Annunciator control modules
Table of Contents

Advertisement

Program Mapping

Program Mapping
Annunciator points "track" or follow those system points they are
programmed to annunciate; they do not latch. The table outlines the
annunciation of system functions.
Note: Control Switches marked "No Function" will still function as local LAMP TEST
or local ACKNOWLEDGE switches for their respective points.
Annunciator
1
Point
Point #1
Point #2
Point #3
Point #4
Point #5
Point #6
Point #7
Point #8
1. If the Eight-Point Shift (DIP switch # 4) is set "ON," the eight CPU functions will be shifted from
annunciator points 1 through 8 to points 57 through 64 (provided those points exist in the system).
2. These control switches are active only if: DIP Switch #5 (Receive Only) is 'OFF' and DIP Switch
#7 (Switch Inhibit) is 'OFF'.
3. Supervisory Point lights its associated zone red LED and annunciator point #5 yellow
LED.
Table 7 Annunciator Program Mapping - MS-9600
ACM-16ATF/ACM-32AF Manual PN 51480:A0 02/02/01
ACM-16ATF & AEM-16ATF
ACM-32AF
AEM-32AF
Red LED
Indicates System
Alarm
Not used
Not used
Not used
Not Used
Not Used
Not Used
Not Used
Appendix D: MS-9600
Yellow LED
Indicates System
Trouble
Indicates Alarm
Silenced
Indicates Program
Mode
Indicates Supervisory
3
Condition
Indicates NAC
Trouble
Indicates Walktest
Indicates Low Battery No Function
Indicates AC Fail
2
Control Switch
ACKNOWLEDGE
ALARM SILENCE
SYSTEM RESET
DRILL
No Function
No Function
No Function
59