Appendix B: Sensiscan 2000
Capabilities
When installed with a Sensiscan 2000, the modules can annunciate the status
of initiating and notification circuits, relays, and several system control
functions. Each annunciator LED is automatically assigned to one and only
one system point.
Note: To operate the annunciator module, the CPU must be Revision D or greater.
The revision level of the CPU is marked on a label affixed to the upper board.
Additionally, the system must be operating under CPU software with U4 ROM part
number 73085 or higher.

Circuits:

• IZM-8F Initiating Device Circuits (alarm and trouble)
• ICM-4F / ICE-4F Notification Appliance Circuits (trouble)*
• CRM-4F / CRE-4F Control relays (trouble)*
• TCM-2F circuits (trouble)*
• TCM-4F circuits (trouble)*
• VCM-4F / DCM-4F circuits (trouble)*
*Indication of output circuit activation can be obtained by
programming the CPU for "OUTPUT STATUS."

System Controls:

• Acknowledge
• Signal Silence
• System Reset
• Activate Notification Circuits 1 and 2, the Remote Signaling Municipal
Tie circuit, and the Alarm Relay.

Configuring for the Sensiscan 2000

The annunciator can be set for addresses 1 or 2. The actual mapping
arrangement for a respective annunciator module and its expanders depends
on System annunciator programming. Refer to the Sensiscan 2000 Manual
for a more detailed explanation.
ACM-16ATF/ACM-32AF Manual PN 51480:A0 02/02/01