(5-3) Explanation of each P parameter
[P001], [P002]
What to do in case of an option error
"00" : Make inverter trip when an option error.
"01" : Make inverter ignore the error.
[P001] is for option slot 1, and [P002] is for option slot 2.
[P010]
Function display selection related to SJ-FB under user parameter [U***] mode
"00" : Parameters related to SJ-FB do not appear on the panel.
"01" : Parameters related to SJ-FB appear on the panel.
This is nothing to do with the actual performance of the motor control. It is only a display issue.
[P011]
Pulse numbers of the encoder (ppr)
Suitable number should be set depending on the encoder to be used.
[P012]
SJ-FB control mode under V2 control mode
"00" : ASR (Speed control) mode
"01" : APR (Position control) mode
[P013]
Pulse train mode of the encoder
"00" : 90 of phase difference pulse train input
SAP
SAN
SBP
SBN
Detected
pulse numbers
"01" : FW/RV pulse and pulse train
SAP
SAN
SBP
SBN
Detected
pulse numbers
© 2002 Hitachi America, Ltd.
Forward
Reverse
Forward
Reverse
21
Pulse train input
FW/RV signal