Flue, System Size 60, 80 And 100 (Components) (Type B 23 /B 33 2008) - Viessmann Vitodens series Technician Manual

Flue systems for gas condensing boilers 3.8 to 105.0 kw
Hide thumbs Also See for Vitodens series:
Table of Contents

Advertisement

Design and sizing information for connection on the flue gas side
Flue, system size 60, 80 and 100 (components) (type B
2
1
5 4
6
A
C
D
A
A Ventilation air
For sizing the air vent, see page 29
B Flue gas
C Inspection port
D Connection piece
E Secondary ventilation
Max. total length of the flue pipe
Vitodens 200-W, 222-F, 222-W, 242-F and Vitosolar 200-F
Rated output range
max. length - system size 60
max. length - system size 80
max. length - system size 100
Vitodens 300-W, 333-F and 343-F
Rated output range
max. length - system size 60
max. length - system size 80
*1
Alternative system size: order balanced flue adaptor separately.
VIESMANN
30
B
E
2
3
C
4
2
3
2
3
E
2
2
E
kW
4.8–19.0
m
20
m
*1
25
m
kW
m
m
/B
according to TRGI 2008)
23
33
1
Boiler flue connection (part of the
standard boiler delivery)
2
Standard shaft set (PPs, rigid)
Comprising:
– Support bend
– Support rail
– Shaft cover
– Spacers (3 pce, max. distance 5 m)
or
Standard shaft pack (metal/PPs,
rigid)
for twin draught chimneys; one
draught for solid fuel boilers
comprising:
– Support bend
– Support rail
– Shaft cover (metal)
– Terminal pipe (stainless steel)
– Spacers (3 pce, max. distance 5 m)
Spacers (3 pce, max. distance 5 m)
3
Flue pipe
1.95 m long
(2 pce @ 1.95 m = 3.9 m)
1.95 m long (1 pce)
1 m long (1 pce)
0.5 m long (1 pce)
4
Inspection piece, straight (1 pce)
5
Flue bend
87º (1 pce)
45º (2 pce)
or
Inspection tee
87º (1 pce)
or
Inspection bend
87º (1 pce)
6
Ventilation bezel (1 pce)
Flue bend (for use in corbelled chim-
neys)
30º (2 pce)
15º (2 pce)
Stainless steel extension, 380 mm
long for shaft cover, standard shaft
pack (metal/PPs, rigid)
(for system size 60, an extension Ø
60 mm to Ø 80 mm is required)
Extension
– Ø 60 mm to Ø 80 mm
– Ø 80 mm to Ø 100 mm
6.5–26.0
8.8–35.0
13.0–45.0
20
15
*1
*1
25
25
25
*1
25
3.8–13.0
3.8–19.0
15
*1
17
(cont.)
System size Ø mm
60
80
100
60
80
100
60
80
100
60
80
100
60
80
100
60
80
100
60
80
100
60
80
100
60
80
100
60
80
100
60
80
100
60
80
100
60
80
100
60
80
100
60
80
80
100
17.0–60.0
30.0–80.0
30.0–105.0
15
*1
20
20
5.2–26.0
7.0–35.0
15
15
*1
*1
17
20
VITODENS
20
11
*1
15

Hide quick links: