Design and sizing information for connection on the flue gas side
Roof outlet for shafts with Promat profiles
C
2
A Vertical coaxial roof outlet (balanced flue system)
B Universal roof tile
C Lightweight shaft made from PROMATECT® mineral fibre pro-
files
2.6 Plastic (PPs) balanced flue system for routing multiple pipes through a shaft
There is an option of routing several flues in balanced flue mode
through a common, sufficiently sized shaft. For this, the Vitodens con-
densing boilers must be installed in the same living space. For reasons
of fire protection, the installation and connection on different levels or
in different rooms is not possible. The flues and the shaft covers must
be professionally supported inside/on the shaft. For balanced flue
components from the Vitodens to the common shaft, see page 13.
Layout examples
Minimum clearances of the individual flues to DIN V 18160-1:
■ In square/rectangular shafts: 20 mm
■ In round shafts: 30 mm
VIESMANN
24
A
B
(cont.)
During installation, match the final shaft profile to the roof pitch.
≥ 30
≈ 150
A Ventilation air
B Flue gas
C Inspection port
VITODENS