Program Mode
Output Relay Function Selections (88)
The Output Relay can be programmed to activate for any one of six conditions. It can be programmed to 0, 1, 2 or
4 to match one of the input channels or it can be programmed to 6 or 7 for DACT functioning. The factory default
for address 88 is '7' for activation on DACT trouble. Program a '0' for fire alarm; '1' for host control panel trouble;
'2' for fire supervisory: '4' for AC Loss; '6' for total communication failure
Trouble Call Limit (89)
Factory default setting of '0' in address 89, allows the digital communicator to call the Central Station each time
any DACT trouble and any active Channel programmed for host panel trouble is detected by the 411. Program-
ming a '1' in this address enables the Trouble Call Limit feature, which limits the number of 411 and Input Chan-
nel Trouble calls to the Central Station to 10 calls for each unique trouble event within a 24 hour period. Separate
limit counters keep track of each unique type of trouble (i.e. open input channel). To clear the limit counters, dis-
able and then enable this location. Note that the number of phone line (communication) faults called to the Cen-
tral Station are not limited by this feature.
No subsequent restoral message is sent to the Central Station(s) for a particular trouble whose limit of 10 calls has
been reached. Local DACT annunciation will still track the particular trouble and restoral.
Reserved for Future Use (90 - 93)
Reserved for Future Use (94 - 113)
Reserved for Future Use (114 - 115)
Reserved for Future Use (116)
Reserved for Future Use (117 - 136)
Reserved for Future Use (137)
Programming Event Code Settings (138 - 265)
Event Code Settings, corresponding to the Formats selected for the Primary Central Station phone number in
address 20 and the Secondary Central Station phone number in address 50, are automatically set to factory default
values. Refer to Table 3-2, "4+2 Standard and 4+2 Express Formats - Primary," on page 28, Table 3-3, "All 3+1,
4+1 and 4+2 Expanded Formats - Primary," on page 29 and Table 3-1, "Ademco Contact ID Format - Primary,"
on page 28 for format designated by address 20. Refer to Table 3-5, "4+2 Standard and 4+2 Express Formats -
Secondary," on page 32, Table 3-6, "All 3+1, 4+1 and 4+2 Expanded Formats - Secondary," on page 33 and Table
3-4, "Ademco Contact ID Format - Secondary," on page 31 for format designated by address 50. The Event Code
Settings can be altered. Consult your Central Station prior to changing the event code settings.