Fire-Lite 411 Manual page 30

Digital alarm communicator/transmitter
Hide thumbs Also See for 411:
Table of Contents

Advertisement

Program Mode
Primary Central Station Number 24 Hour Test Time (25 - 28)
Use military time when entering the 24 hour 'test' time. The 24 hour test report to phone number 1 takes up four
locations, from addresses 25 - 28. The default is 00:00 (12:00 midnight). The limits for each location are as fol-
lows (do not use values of A - F as entries).
25: enter 0, 1 or 2
26: enter 0 - 9
27: enter 0 - 5
28: enter 0 - 9
Primary Central Station Number 24/12/8/6 Hour Test Time Interval (29)
The test report sent to the Primary phone number may be sent every 6, 8, 12 or 24 hours. If the message is to be
sent every 24 hours, leave the factory default entry of '0'. If other test report times are needed, enter 1 = 12 hour,
2 = 8 hour or 3 = 6 hour.
Secondary Central Station Phone Number (30 - 49)
Addresses 30 - 49 are factory set to 'F' (30_F to 49_F). Programming is typically done as follows:
If your phone number is 484-7161, press 4.
The display will read 30_4.
Press [ENTER/STORE] to save the entry to memory and increment to the next address 31_F.
Enter the remaining numbers in their respective addresses as shown below:
4
Entry
30 31 32 33 34
Address
Valid entries for both the primary and secondary phone numbers are 0 to 9 and A to F with the numeric digits as
dialed numbers and the hexadecimal digits representing the following functions:
• A = * on a Touch-Tone phone keypad
• B = # on a Touch-Tone phone keypad
• C = look for secondary dial tone for up to two seconds (then dial anyway)
• D = three second pause
• E = five second pause
• F = end of phone number (Note: F must remain in all unused phone number addresses)
30
8
4
7
1
6
1
F
35 36
37 38 39 40
411 Communicator
F
F
F
F
F
F
41
42 43 44 45 46 47
Document #50921
Rev. E
12/09/2008
F
F
F
F
F
F
48 49
P/N 50921:E

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents