Fire-Lite 411 Manual page 34

Digital alarm communicator/transmitter
Hide thumbs Also See for 411:
Table of Contents

Advertisement

Program Mode
Secondary Central Station Number 24/12/8/6 Hour Test Time Interval (59)
The test report sent to the Secondary phone number may be sent every 6, 8, 12 or 24 hours. If the message is to be
sent every 24 hours, leave the factory default entry of '0'. If other test report times are needed, enter 1 = 12 hour,
2 = 8 hour or 3 = 6 hour.
AC Loss Reporting Delay (60)
Enter a digit of 0 - 9 or A - F corresponding to the number of hours to be delayed in reporting the loss of AC
power. The factory default is '0' for no delay. The valid entries are '0' = no delay; '1' = 1 hours; '2' = 2 hours;
'3' = 6 hours; '4' = 7 hours; '5' = 8 hours; '6' = 9 hours; '7' = 10 hours; '8' = 11 hours; '9' = 12 hours; 'A' = 13 hours;
'B' = 14 hours; 'C' = 15 hours; 'D' = 16 hours; 'E' = 17 hours; 'F' = 18 hours. Note: Use when the host panel has a
dedicated relay output. Verify the delay period programmed at the host panel. Location 60 is valid for all inputs
programmed as AC Loss.
Backup Reporting (61)
Leaving address 61 at '0' means that reports will be transmitted to the secondary Central Station phone number
only if attempts to communicate to the primary Central Station phone number are unsuccessful. Programming a
'1' causes all reports to be transmitted to both the primary and secondary Central Station phone numbers. Pro-
gramming a '2' causes reports to go to the first available receiver.
!
CAUTION: Do not alter this entry while the digital communicator is active.
Reserved for Future Use (62)
Reserved for Future Use (63)
Communicator Enable/Disable (64)
Leaving address 64 at the factory default setting of '0' prevents the digital communicator from transmitting status
information to the Central Station(s). An entry of '1' in this location enables communication to the Central
Station(s).
Note that upon power-up, the 411 will immediately annunciate a DACT trouble since the communicator is factory
defaulted to 'communicator disabled' at program location 64.
Input Channel Function Selections - When selecting Input Channel functions, be certain to match the host panel
relay output functions with the Input Channel functions. Test all wiring connections completely. All Input Channels
require Normally Open contact closure to trigger. Input Channels do not latch.
Input Channel 1 Function Selection (65)
Factory default for Channel 1 is '0' for activation on Fire Alarm. Enter '1' for Host Control Panel Trouble; '2' for
Fire Supervisory; '4' for AC Loss.
Input Channel 2 Function Selection (66)
Factory default for Channel 2 is '1' for activation on Host Control Panel Trouble. Enter '0' for Fire Alarm; '2' for
Fire Supervisory; '4' for AC Loss.
Input Channel 3 Function Selection (67)
Factory default for Channel 3 is '2' for activation on Fire Supervisory. Enter '0' for Fire Alarm; '1' for Host Control
Panel Trouble; '4' for AC Loss.
1. Changing the input function will automatically change the corresponding Primary and Secondary event codes to reflect the new
input function. The Communication Format should be programmed first, followed by the Input Channel Function.
34
1
1
1
411 Communicator
Document #50921
Rev. E
12/09/2008
P/N 50921:E