INSTALLATION

Step 1 — Check Perfect Air Air Purifier Components
CAUTION
!
PERSONAL INJURY HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care and
wear appropriate protective clothing and gloves when
handling parts.
Carefully remove all items from the box.
Step 2 — Identify Mounting Location
a. Identify a mounting orientation for the Perfect Air Air Purifier
in the return air duct (see Fig. 4).
b. Ensure airflow direction through the Perfect Air Air Purifier
matches the arrows on the face of the air purifier cartridge.
The Perfect Air Air Purifier or door can be rotated 180_ to
accommodate the cabinet orientation.
Airflow
Downflow
Mounting Cabinet Vertical
A06517
Horizontal
Fig. 4 - - Perfect Air Air Purifier Cabinet Orientation
Return Duct
Adapters (x4)
A06389
Fig. 5 - - Mounting Perfect Air Air Purifier Cabinet For Fan Coils
c. The location of the Perfect Air Air Purifier should be readily
accessible. Enough room should be provided for periodic re-
placement of the air purifier cartridges.
Step 3 — Mount Cabinet
a. Turn off power to the heating and cooling system.
b. Remove the existing fan coil filter and discard. Excessive sys-
tem static pressure may result if the Perfect Air Air Purifier is
used with other filtration devices.
c. Remove the air purifier cartridge and enhancement module
from the Perfect Air Air Purifier cabinet.
d. Position the cabinet between the fan coil and return air duct
(see Fig. 4 and 5). A transition duct may be required.
NOTE: The fan coil cabinet screws holding the filter rack should
be used to attach the air purifier cabinet.
a. Gasket tape between the fan coil and the air purifier cabinet is
already factory installed.
b. Mounting holes are provided for fan coil attachment.
c. Use return duct adapters provided to attach return ductwork
(See Fig. 6).
d. Seal seams with tape or caulking after the Perfect Air Air Puri-
fier cabinet has been secured.
A irf lo w
A06371
Return Duct
Adapters (x4)
Mounting Cabinet Horizontal
3
Airflow
A06374
Upflow
A06388