Start-Up Checklist - Bryant 551A Installation, Start-Up And Service Instructions Manual

Durapac plus series sizes 155-240 single package rooftop electric cooling/electric heating units
Hide thumbs Also See for 551A:
Table of Contents

Advertisement

MODEL NO.:
DATE:
I. PRE-START-UP:

VERIFY THAT ALL PACKING MATERIALS HAVE BEEN REMOVED FROM UNIT

VERIFY INSTALLATION OF INDOOR FAN MOTOR ADJUSTMENT BOLT (155 UNITS) OR ADJUSTMENT
BOLT AND PLATE (180, 240 UNITS)

VERIFY INSTALLATION OF OUTDOOR AIR HOOD

VERIFY THAT CONDENSATE CONNECTION IS INSTALLED PER INSTRUCTIONS

VERIFY THAT ALL ELECTRICAL CONNECTIONS AND TERMINALS ARE TIGHT

CHECK THAT FILTERS AND SCREENS ARE CLEAN AND IN PLACE

VERIFY THAT UNIT IS LEVEL

CHECK FAN WHEEL AND PROPELLER FOR LOCATION IN HOUSING/ORIFICE, AND VERIFY SETSCREW
IS TIGHT

VERIFY THAT FAN SHEAVES ARE ALIGNED AND BELTS ARE PROPERLY TENSIONED

VERIFY THAT SCROLL COMPRESSORS ARE ROTATING IN THE CORRECT DIRECTION

VERIFY THAT CRANKCASE HEATER HAS BEEN ENERGIZED FOR 24 HOURS
II. START-UP:
ELECTRICAL
SUPPLY VOLTAGE
COMPRESSOR AMPS — COMPRESSOR NO. 1 L1
— COMPRESSOR NO. 2 L1
SUPPLY FAN AMPS
ELECTRIC HEAT AMPS (IF SO EQUIPPED)
TEMPERATURES
OUTDOOR-AIR TEMPERATURE
RETURN-AIR TEMPERATURE
COOLING SUPPLY AIR
ELECTRIC HEAT SUPPLY AIR (IF SO EQUIPPED)
PRESSURES
REFRIGERANT SUCTION
REFRIGERANT DISCHARGE CIRCUIT NO. 1

VERIFY REFRIGERANT CHARGE USING CHARGING CHART ON PAGE 29.
GENERAL

ECONOMI$ER MINIMUM VENT AND CHANGEOVER SETTINGS TO JOB REQUIREMENTS

VERIFY INSTALLATION OF ALL OPTIONS AND ACCESSORIES
Copyright 2001 Bryant Heating & Cooling Systems

START-UP CHECKLIST

L1-L2
EXHAUST FAN AMPS
L1
F DB (Dry-Bulb)
F DB
F
CIRCUIT NO. 1
PSIG
PSIG
SERIAL NO.:
TECHNICIAN:
L2-L3
L2
L2
L2
F WB (Wet-Bulb)
F
CIRCUIT NO. 2
CIRCUIT NO. 2
CL-1
L3-L1
L3
L3
L31
PSIG
PSIG
CATALOG NO. 5355-105