MODEL NO.: ___________________________________________
DATE: _________________________________________________
I. PRE-START-UP:
VERIFY THAT ALL PACKING MATERIALS HAVE BEEN REMOVED FROM UNIT
VERIFY INSTALLATION OF OUTDOOR AIR HOOD
VERIFY INSTALLATION OF FLUE EXHAUST AND INLET HOOD
VERIFY THAT CONDENSATE CONNECTION IS INSTALLED PER INSTRUCTIONS
VERIFY THAT ALL ELECTRICAL CONNECTIONS AND TERMINALS ARE TIGHT
VERIFY GAS PRESSURE TO UNIT GAS VALVE IS WITHIN SPECIFIED RANGE
CHECK GAS PIPING FOR LEAKS
CHECK THAT INDOOR-AIR FILTERS ARE CLEAN AND IN PLACE
CHECK THAT OUTDOOR AIR INLET SCREENS ARE IN PLACE
VERIFY THAT UNIT IS LEVEL
CHECK FAN WHEEL AND PROPELLER FOR LOCATION IN HOUSING/ORIFICE, AND VERIFY SETSCREW
IS TIGHT
VERIFY THAT FAN SHEAVES ARE ALIGNED AND BELTS ARE PROPERLY TENSIONED
VERIFY THAT SCROLL COMPRESSORS ARE ROTATING IN THE CORRECT DIRECTION
VERIFY INSTALLATION OF THERMOSTAT
VERIFY THAT CRANKCASE HEATERS HAVE BEEN ENERGIZED FOR AT LEAST 24 HOURS
II. START-UP
ELECTRICAL
SUPPLY VOLTAGE
COMPRESSOR AMPS — COMPRESSOR A1
— COMPRESSOR B1
— COMPRESSOR C1
(210,240 ONLY)
SUPPLY FAN AMPS ___________
TEMPERATURES
OUTDOOR-AIR TEMPERATURE
RETURN-AIR TEMPERATURE
COOLING SUPPLY AIR
GAS HEAT SUPPLY AIR
PRESSURES
GAS INLET PRESSURE
GAS MANIFOLD PRESSURE STAGE NO. 1
REFRIGERANT SUCTION
REFRIGERANT DISCHARGE CIRCUIT A
VERIFY REFRIGERANT CHARGE USING CHARGING CHARTS ON PAGE 40
GENERAL
ECONOMIZER MINIMUM VENT AND CHANGEOVER SETTINGS TO JOB REQUIREMENTS
Copyright 2005 Bryant Heating & Cooling Systems

START-UP CHECKLIST

L1-L2
L2-L3
L1
L1
L1
F DB (Dry Bulb)
F DB
F
F
IN. WG
IN. WG
CIRCUIT A
PSIG
CIRCUIT B
PSIG
CIRCUIT C
PSIG (210,240 ONLY)
PSIG
CIRCUIT B
PSIG
CIRCUIT C
PSIG (210,240 ONLY)
CL-1
SERIAL NO.: ______________________________________________
TECHNICIAN:_____________________________________________
L3-L1
L2
L2
L2
F WB (Wet Bulb)
STAGE NO. 2
Printed in U.S.A.
L3
L3
L3
IN. WG
CATALOG NO. 04-53581005-01

Advertisement

Table of Contents
loading

Table of Contents