COLLECTOR BOX
DRAIN TUBE (BLUE)
CAP
PLUG
COLLECTOR BOX
TUBE (GREEN)
COLLECTOR BOX
TUBE (PINK)
COLLECTOR BOX
DRAIN TUBE (BLUE
& WHITE STRIPED)
COLLECTOR BOX
EXTENSION TUBE
CONDENSATE
TRAP
INDUCER HOUSING
DRAIN TUBE (VIOLET)
Fig. 9 - - Downflow Tube Configuration
(Left- -Hand Trap Installation)
Condensate Trap Location
The condensate trap must be removed from the factory- -installed
blower shelf location and relocated in selected application location
as shown in Fig. 2, 9, or 10.
To relocate condensate trap from the blower shelf to desired
location, perform the following:
1. Remove 3 tubes connected to condensate trap.
2. Remove trap from blower shelf by gently pushing tabs in-
ward and rotating trap.
3. Remove casing hole filler cap from casing hole. (See Fig. 2
and 10.)
4. Install casing hole filler cap (factory- -supplied in loose parts
bag) into blower shelf hole where trap was removed.
WARNING
!
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury
or death.
Casing hole filler cap must be installed in blower shelf hole
when condensate trap is relocated to prevent combustion
products being drawn in from appliances in the equipment
room
5. Install condensate trap into left- -hand side casing hole by
inserting tube connection stubs through casing hole and
rotating until tabs snap into locking position.
6. Fill unused condensate trap casing holes with plastic filler
caps (factory- -supplied in loose parts bag).
DRAIN TUBE
COUPLING
A94215
Fig. 10 - - Downflow Tube Configuration
(Right- -Hand Trap Installation)
Condensate Trap Tubing
NOTE: See Fig. 9 or 10 or tube routing label on main furnace
door to check for proper connections.
1. Collector Box Drain Tube
a. Remove factory- -installed plug from LOWER collector
box drain tube (blue and white striped label).
b. Install removed clamp and plug into UPPER collector
box drain tube (blue label) which was connected to
condensate trap.
c. Connect LOWER collector box drain connection to
condensate trap.
S Condensate Trap Located on Left Side of Casing
a. Connect LOWER collector box drain tube (blue and white
striped label) to condensate trap. Tube does not need to be
cut.
b. Clamp tube to prevent any condensate leakage.
S Condensate Trap Located on Right Side of Casing
a. Install drain tube coupling (factory- -supplied in loose parts
bag) into collector box drain tube (blue and white striped
label) which was previously plugged.
b. Connect larger diameter drain tube (factorysupplied in loose
parts bag) to drain tube coupling, extending collector box
drain tube for connection to condensate trap.
c. Route extended collector box drain tube between gas valve
and inlet housing as shown in Fig. 10.
d. Determine appropriate length and cut.
e. Connect to condensate trap.
f. Clamp tube to prevent any condensate leakage.
2. Inducer Housing Drain Tube
a. Remove factory- -installed cap and clamp from LOWER
inducer housing drain connection.
10
COLLECTOR BOX
TUBE (GREEN)
PLUG
CAP
COLLECTOR BOX
DRAIN TUBE (BLUE)
COLLECTOR BOX
TUBE (PINK)
COLLECTOR BOX
DRAIN TUBE (BLUE
& WHITE STRIPED)
COLLECTOR BOX
EXTENSION TUBE
INDUCER HOUSING
DRAIN TUBE
(VIOLET)
CONDENSATE
TRAP
COLLECTOR BOX
EXTENSION
DRAIN TUBE
A94216