Bryant 619E Preliminary Product Data page 16

Sizes 009-024 3/4 to 2 tons high wall duct-free, split systems
Table of Contents

Advertisement

INDOOR
UNIT
619E
009†
012†
009**
012**
018†
024†
018**
024**
LEGEND
FLA
— Full Load Amps
HACR — Heating, Air Conditioning, Refrigeration
LRA
— Locked Rotor Amps
MCA
— Minimum Circuit Amps per NEC Section 430-24
NEC
— National Electrical Code
RLA
— Rated Load Amps (Compressor)
*Permissible limits of the voltage range at which unit will operate
satisfactorily.
†Cooling only fan coil unit.
**Heat pump fan coil unit.
ELECTRICAL DATA (cont)
FAN COIL UNITS
V (Single-
Ph, 60 Hz)
115
208/230
115
208/230
208/230
OPERATING VOLTAGE*
Minimum
104
187
104
187
187
NOTES:
1. The 018, 024, 048 outdoor units contain a 24-v transformer; addi-
tional transformers are not required. The 009, 012 outdoor units use
230-v (high voltage) controls.
2. All motors and compressors contain internal overload protection.
3. In compliance with NEC requirements for multimotor and combina-
tion load equipment (refer to NEC Articles 430 and 440), the over-
current protective device for the unit shall be fuse or HACR breaker.
4. Motor RLA values are established in accordance with UL (Underwrit-
ers' Laboratories) Standard 1995.
16
Maximum
127
253
127
253
253
FAN
FLA
0.53