General InstructIOns

ImPOrtant

The equipment covered in this manual is to be installed
by trained, experienced service and installation
technicians. All duct work, supply and return
ducts, must be properly sized for the design airflow
requirement of the equipment. ACCA is an excellent
guide to proper sizing. All duct work or portions
thereof not in the conditioned space should be properly
insulated in order to both conserve energy and prevent
condensation or moisture damage.

shIPPInG DamaGe

Upon receipt of equipment, the carton should be
checked for external signs of shipping damage. If
damage is found, the receiving party must contact
the last carrier immediately, preferably in writing,
requesting inspection by the carrier's agent.

General

The refrigerant system is completely assembled and
charged. All internal wiring is complete.
The unit is designed for use with or without duct work.
Flanges are provided for attaching the supply and return
ducts.
These instructions explain the recommended method
to install the air cooled self-contained unit and the
electrical wiring connections to the unit.
These instructions and any instructions packaged with
any separate equipment required to make up the entire
system should be carefully read before beginning the
installation. Note particularly "Starting Procedure" and
any tags and/or labels attached to the equipment.
While these instructions are intended as a general
recommended guide, they do not supersede any national
and/or local codes in any way. Authorities having
jurisdiction should be consulted before the installation
is made.
Manual 2100-467K
Page
4 of 24
FIelD InstalleD heater PacKaGes
(OPtIOnal)
These packaged air conditioners are manufactured
without supplementary electric heaters. Supplementary
heaters are available for simple, fast field installation.
A separate power circuit is required for the
supplementary heaters.
IMPORTANT: Refer to Table 1 when designing duct
work for maximum available static pressure with heater
installed.
Refer to data shown in Table 3 and 4 for proper
application information on all available heater
combinations and what units they can be used with. It
also shows the applicable circuit ampacities, fuse size,
and wire size for each heater combination.
table 1
rateD cFm anD external statIc Pressure
(esP)
model
rated
recommended
no.
cFm
Airflow Range
PA1324
800
PA1330
1000
PA1336
1100
PA1342
1450
PA1348
1550
PA1360
1750
NOTE: ECM motors provide rated CFM up to 0.50 ESP
rated
max.
esP
esP
Note
0.18
0.50
0.23
0.50
Note
Note
0.23
0.50
Note
0.23
0.50
0.28
0.50
Note
Note
0.28
0.50