Replacement parts manual
dc free cooling unit system
two (2) d-series dual-tec™
wall-mounted package
one (1) bard-linktm plc
lead/lag controller
controller models
lc1000-100/bld.10293, lc1500-100/bld.10291 (107 pages)
CONTENTS Start Up and Operation Getting Other Informations and Publications Three Phase Scroll Compressor Start Up General Instructions Information ............. 17 Important ..............2 Sequence of Operation .......... 17 Shipping Damage ............ 2 Start Up Notes ............17 General ..............2 Indoor Blower Motor ..........
Getting Other Information and Publications These publications can help you install the air FOR MORE INFORMATION, CONTACT conditioner or heat pump. You can usually find these at THESE PUBLISHERS: your local library or purchase them directly from the publisher. Be sure to consult current edition of each ACCA Air Conditioning Contractors of America standard.
GENERAL INSTRUCTIONS IMPORTANT FIELD INSTALLED HEATER PACKAGES (OPTIONAL) The equipment covered in this manual is to be installed by trained, experienced service and installation These packaged air conditions are manufactured technicians. All duct work, supply and return ducts, without supplementary electric heaters. Supplementary must be properly sized for the design air flow heaters are available for simple, fast field installation.
TABLE 2B ELECTRICAL SPECIFICATIONS – – a t l i n i t i u y t i – t i n – – l l o l l o l l o l l o l l o l l o l l o s t l –...
Page 8
TABLE 3 OPTIONAL FIELD INSTALLED HEATER PACKAGES ONLY TO BE USED WITH THE MODELS INDICATED & . y l & S = Standard Application – Heater volts and phase same as basic unit A Alternate Application – Heater volts and phase different from basic unit. N = Not Approved...
Page 9
TABLE 4 OPTIONAL FIELD INSTALLED ELECTRIC HEATER TABLE . r t & . r t & . r t Time Delay fuses of “HACR” type circuit breakers must be used for 60 and smaller sizes. Standard fuses or circuit breakers are suitable for sizes 70 and larger.
INSTALLATION LOCATION TYPICAL INSTALLATIONS GENERAL 1. ROOF MOUNTED – The unit is mounted on a sturdy base on the roof of the building. Return air The unit must be located outside, or in a well ventilated to the unit is brought through a single return grille area.
FIGURE 6 PREFABRICATED ROOF CURB SPECIFICATIONS HEAVY GAUGE GALVANIZED WITH WOOD NAILING STRIP, WELDED/LEAKPROOF ONCE PIECE CONSTRUCTION – READY TO INSTALL MIS-1177C...
TABLE 6 ROOF CURB DETAILS (Refer to Figure 7) FIGURE 7 FIELD FABRICATED CURBING A SEPARATE METAL FLASHING SHOULD BE INSTALLED AROUND WOOD CURBING. CAULK AND SEAL ALL JOINTS AND WEATHERPROOF. TABLE 7 DIMENSION FOR X IN FIG. 7 MIS-1178A Manual 2100-353 Page...
5. OTHER INSTALLATIONS – Many other Prior thought should be given to return air location and installations are possible with the packaged air placement of the air filter(s). The air filter(s) must be conditioner. No matter what the installation, always of adequate size and readily accessible to the operator consider the following facts: of the equipment.
TABLE 9 WIRING – MAIN POWER THERMOSTAT WIRE SIZE Refer to the unit rating plate for wire sizing information and maximum fuse size. Each outdoor unit is marked with a “Minimum Circuit Ampacity”. This means that the field wiring used must be sized to carry that amount of current.
START UP AND OPERATION START UP NOTES THREE PHASE SCROLL COMPRESSOR START UP INFORMATION For improved start up performance, wash the indoor coil with dishwasher detergent. Scroll compressors, like several other types of compressors, will only compress in one rotational direction.
LOW PRESSURE SWITCH, BYPASS, AND ADJUSTMENTS LOCKOUT SEQUENCE ADJUSTABLE DELAY-ON-MAKE AND NOTE: The low pressure switch is an optional control DELAY-ON-BREAK TIMER and the bypass and lockout sequence are part of the standard compressor control module. The potentiometer is used to select Delay-on-Break time from 30 seconds to 5 minutes.
SERVICE AND TROUBLESHOOTING SERVICE HINTS FAN BLADE SETTINGS Shown in Figure 10 are the correct fan blade setting 1. Caution homeowner to maintain clean air filters at dimensions for proper air delivery across the outdoor all times. Also, not to needlessly close off supply coil.
– Reinsert tube into fitting. SUCTION AND DISCHARGE TUBE BRAZING – Heat tube uniformly in Area 1 moving slowly to Area 2. When joint reaches brazing Compliant Scroll compressors have copper plated steel temperature, apply brazing material. (See suction and discharge tubes. These tubes are far more Figure 11) rugged and less prone to leaks than copper tubes used on other compressors.
TROUBLESHOOTING ECM BLOWER MOTORS CAUTION Disconnect power from unit before removing or replacing connectors, or servicing motor. Wait at least 5 minutes after disconnection power before opening motor. a t l a t l t ' n a i l a l l .