Manual Start/Stop; Automatic Start/Stop; Automatic Fault Shutdown - Baldor GLC30 Installation & Operating Manual

Glc generator (gaseous liquid cooled)
Hide thumbs Also See for GLC30:
Table of Contents

Advertisement

Manual Start/Stop

To manually Start the Gen–Set, set the Master Control switch to the "Manual Run" position. The
following happens:
To manually Stop the Gen–Set, set the Master Control switch to the "Stop" position. The
controllers RUN output will be immediately terminated which will initiate the engine stop
sequence. The engine is locked out and will not run with the Master Control switch in "Stop".

Automatic Start/Stop

To setup the generator for automatic operation, set the Master Control switch to the "Auto Start"
position. The following happens:

Automatic Fault Shutdown

When a fault circuit is programmed as a SHUTDOWN, the engine will immediately stop when the
fault is activated. A specific shutdown fault can be programmed with a definite time transient
delay period that must expire before the shutdown is activated. The stop sequence will cause the
controllers RUN output to be immediately terminated which will cause the engine to stop.
Fuel Relay
Start Relay
High Water
Temperature
Low Oil
Pressure
Magnetic
Pickup
MN2408
1.
When the "Manual Run" push–button is pressed, an Engine Start Delay timer is
initiated. (The start sequence will not be initiated if any shutdown fault condition is
present.)
2.
When the engine start delay time expires, an engine RUN and CRANK output signal
will be initiated. (The RUN output may be programmed to only energize when a start
signal is initiated and an engine speed signal is detected.)
3.
When the engine starts and begins to accelerate to nominal speed, the controllers
speed sensor will terminate the CRANK output when engine speed reaches
approximately 20% speed (i.e. CRANK DISCONNECT speed setpoint).
1.
The engine will automatically start upon activation of the remote start contact input. The
remote device initiates a start sequence upon contact closure.
2.
When the remote start signal is activated, the engine will start as per the sequence of
operation described for the manual start sequence.
3.
The automatic stop sequence will be initiated by removal of the remote start signal.
4.
When the start signal is removed, a cool down delay function will be initiated.
5.
When the cool down time delay period expires (typically 5 minutes), the controllers
RUN output will be immediately terminated which will initiate the engine to stop.
Figure 4-11 9957N Analog Engine Controller Connections
Manual
Off
Auto
15 14 13
Crank Cycle
Crank Disconnect
Overspeed
Oil Pressure Water Temperature Delay
Remote Start
Contact
Display
LED's
X1
Low Oil Pressure
High Water Temperature
11
Overcrank
10
Overspeed
9
RUN (Engine Started – Not Used)
8
7
Common Alarm (Not Used)
Overspeed Verify (Off = True Speed,
On = 13% increase)
Single (On) or Cycle Crank (Off)
Crank Attempts
Operation 4-23