Operator Control Panel (Analog Engine Controller Only); Operating Procedures - Baldor GLC30 Installation & Operating Manual

Glc generator (gaseous liquid cooled)
Hide thumbs Also See for GLC30:
Table of Contents

Advertisement

Operator Control Panel (Analog Engine Controller Only)

Panel Light
VOLTAGE
Battery
Engine
Volts
Temp
Operating Procedures The engine–generator controller is designed to start and stop an engine from either a local
("Manual") or remote ("Automatic") mode. When a start command is issued, the controller issues
a run and crank output signal. The controller then monitors engine speed and when crank
disconnect speed is reached, the crank signal is terminated. While the engine accelerates to
normal speed, the controller continuously monitors the engines speed signal. Should the engine
speed exceed the maximum predetermined setpoint, the overspeed shutdown fault circuit will
activate, terminating the run signal.
In addition to overspeed shutdown, the engine controller also monitors many other engine
protection circuits and should they be activated, the engine will be stopped and/or alarm initiated.
The engine will automatically stop for any shutdown condition, or when the remote and/or local
start signal is removed. The engine controller operation includes time delay circuits for normal
operating conditions such as start delays, cool down and cranking periods.
4-22 Operation
Figure 4-10 Analog Operator Control Panel
HERTZ
AMPERAGE
Oil Pressure
AMMETER
3
PANEL LIGHTS
ON
OFF
PANEL LIGHT
FUSE
RUN TIME (HOURS)
OFF
1
VOLTAGE
2
ADJUST
Panel Light
HIGH TEMPERATURE
LOW OIL PRESSURE
OVERSPEED
OVERCRANK
STOP
MANUAL
AUTO
+
RUN
START
MASTER
CONTROL
MN2408