Operator Control Panel
Operating Procedures The engine–generator controller is designed to start and stop an engine from either a local
("Manual") or remote ("Automatic") modes. When a start command is issued, the controller
issues a run and crank output signal. The controller then monitors engine speed and when crank
disconnect speed is reached, the crank signal is terminated. While the engine accelerates to
normal speed, the controller continuously monitors the engines speed signal. Should the engine
speed exceed the maximum predetermined setpoint, the overspeed shutdown fault circuit will
activate, terminating the run signal.
In addition to overspeed shutdown, the engine controller also monitors many other engine
protection circuits and should they be activated, the engine will be stopped and/or alarm initiated.
The engine will automatically stop for any shutdown condition, or when the remote and/or local
start signal is removed. The engine controller operation includes time delay circuits for normal
operating conditions such as start delays, cool down and cranking periods.

Manual Start/Stop

To manually Start the Gen–Set, push the "RUN" push–button. The following happens:
To manually Stop the Gen–Set, push the "OFF" push–button. The controllers RUN output will be
immediately terminated which will initiate the engine stop sequence.

Automatic Start/Stop

To setup the generator for automatic operation, pressing the "AUTO" push–button.
The following happens:
4-2 Operation
Continued
1.
When the "RUN" push–button is pressed, an ENGINE START DELAY timer is initiated.
(The start sequence will not be initiated if any shutdown fault condition is present.)
2.
When the engine start delay time expires, an engine RUN and CRANK output signal
will be initiated. (The RUN output may be programmed to only energize when a start
signal is initiated and an engine speed signal is detected.)
3.
When the engine starts and begins to accelerate to nominal speed, the controllers
speed sensor will terminate the CRANK output when engine speed reaches
approximately 20% speed (i.e. CRANK DISCONNECT speed setpoint). Immediately
upon reaching crank disconnect speed, the controller will initiate the BYPASS DELAY
time delay function. After the BYPASS DELAY time period (typically 10 seconds) all
fault circuits programmed as BYPASS DELAY=YES are active. (All fault circuits
programmed as BYPASS DELAY=NO are continuously armed irrespective of any
operation sequence.)
1.
The engine will automatically start upon activation of the remote start contact input. The
remote device initiates a start sequence upon contact closure.
2.
When the remote start signal is activated, the engine will start as per the sequence of
operation described for the manual start sequence.
3.
The automatic stop sequence will be initiated by removal of the remote start signal.
4.
When the start signal is removed, a cool down delay function will be initiated.
MN2408