Kenmore 9410 - 30 in. Electric Range Installation Instructions Manual page 4

30" electric range for 3 or 4 wire, 60hz systems
Hide thumbs Also See for 9410 - 30 in. Electric Range:

Advertisement

2A.Models
with
Factory
Connected
Power
Supply
Cord
NOTE:
Some models may be equipped with a factory
connected three (3) conductor power supply cord.
Mobile home installations, new branch circuit installations
(1996NEC) or areas where local codes do not permit
grounding through neutral require a four (4) conductor power
supply cord kit rated at 125/250 volts minimum and marked
for use with ranges. See Range Connection Opening Size
Chart for cord kit ampere rating information. Terminals on
end of wires must be either closed loop or open-end spade
lugs with upturned ends.
2B.Models
Requiring
Power
Supply
Cord Kit
RISK OF FIRE OR ELECTRICAL
SHOCK MAY OCCUR
IF
AN INCORRECT
SIZE RANGE CORD KIT IS USED, THE
INSTALLATION
INSTRUCTIONS
ARE NOT FOLLOWED
OR STRAIN RELIEF
BRACKET
IS DISCARDED.
This appliance may be connected by means of a power
supply cord. Only a power supply cord kit rated at 125/250
volts minimum, and marked for use with ranges shall be
used. See chart on page 3 for cord kit ampere rating
information. Cord must have either three (3) or four (4)
conductors. Terminals on end of wires must be either closed
loop or open-end spade lugs with upturned ends. Cord must
have strain relief clamp.
See section 4A for 3-wire or section 4B for 4-wire connection.
3.
Electrical
Connection
to Range
The rear access cover must be removed. To remove, loosen
center screw (one screw) and remove access cover. The
terminal blockwill then be accessible.
Cover
Rear
of Range
Range Connection
Opening
Size Chart
Supply Cord Kit ampere rating information.
See serial plate on range for
kilowatt rating data.
See Serial Plate on Range for
KW Rating
120/240 Volts 120/208 Volts
8.8-16.5 KW
7.9-12.5
KW
16.6-22.5
KW 12,6-18.5
KW
Cord Kit
Diameter (inches) of Range
Ampere
connection Opening
Rating
Permanent
Cord Kit
Wirinq
40/50 tunp
1-3/8 in.
1-1/8 in.
50 Amp
1-3/8 in.
1-3/8 in,
1-1/8" Dia.
7/8" Dia.
_"
Knockout
Hole
(_)
(See Chart) 4"
Hole _
(See Chart)
Pocket
for Cable
Mounting
Plate
NOTE: Range is shipped from factory with 1-3/8" dia. hole as
shown. To use either 7/8" dia. hole or 1-1/8" dia. knockouts:
If a different diameter hole is required, please follow the
steps below:
1.
Using a 1/4" socketdriver, remove eight(8) screwsfrom
Rear Wall Shield to release from the unit (as shown).
Save the screws for step #7 below.
2. Again usingthe 1/4" socket driver,remove one (1) blunt
pointscrew used to secure the Cable MountingPlate to
the Rear Wall Shield. Save the screws for step #6.
3.
Remove the Cable Mounting Plate from the Rear Wall
Shield by sliding the plate out of the pockets.
4.
If a 1-1/8"dia. hole isrequired,"punch-out"the
knockout.
5.
Rotate the plate 180 degrees so that the desired hole is
placed on top of the opening located on the bottom flange
of the Rear Wal! Shield.
6.
Slide the Cable Mounting Plate into the RearWall Shield.
Re-secure using the blunt point screw removed from step
#2 above.
7.
Reassemble the Rear Wall Shield to the unit using eight
(8) screws removed from step #1 above.
4