ELECTRICAL REQ U IREMENTS AND
HOOK-UP INSTRUCTIONS
ELECTRICAL HOOK -UP INSTRUCTIONS
NOTE: Do not turn on electrical power to your spa until told to do
so later in this manual.
Have a licensed electrician run the required 240 volt power line to the
spa installation site. The power inlet connection is located in the
pedestal on the left side of the spa, approximately 25" from the front.
This connection is designed to mate with a Carlon 1" conduit body Type
LB, Access Fitting E986F or any 1" female PVC conduit fitting.
The manufacturer's label lists the power requirements for your spa. We
recommend that only a licensed and bonded electrician do the initial spa
hook-up.
NOTE: This unit requires a GFCI (Ground Fault Circuit
Inter rupter). We have provided an enclosed instructional flyer for a
licensed electrician. A "line of sight" service disconnect must be located
where visible from the spa, not less than 5 feet from the spa and not to
exceed 50 feet from the spa. This requirement may be filled with the
GFCI sub-panel.
NOTE: All supply wire to be rated minimum 90˚ C.