Checking Gas Connections - Desa Comfort Glow RFP28TC Owner's Operation And Installation Manual

Comfort glow vent-free propane/lp gas radiant flame heater model rfp28tc owner's operation and installation manual
Table of Contents

Advertisement

VENT-FREE RADIANT FLAME
INSTALLATION
Continued
CHECKING GAS
CONNECTIONS
WARNING: Test all gas pip-
ing and connections for leaks
after installing or servicing. Cor-
rect all leaks at once.
WARNING: Never use an open
flame to check for a leak. Apply a
mixture of liquid soap and water
to all joints. Bubbles forming show
a leak. Correct all leaks at once.
CAUTION: Make sure exter-
nal regulator has been installed
between propane/LP supply and
heater. See guidelines under Con-
necting to Gas Supply , page 13.
Pressure Testing Gas Supply
Piping System
Test Pressures In Excess Of 1/2 PSIG
1.
Disconnect heater and its individual
manual shutoff valve from gas supply
piping system. Pressures in excess of
1/2 psig will damage heater regulator.
2. Cap off open end of gas pipe where
manual shutoff valve was connected.
3.
Pressurize supply piping system by ei-
ther using compressed air or opening
propane/LP supply tank valve.
4.
Check all joints of gas supply piping
system. Apply mixture of liquid soap
and water to gas joints. Bubbles form-
ing show a leak.
5.
Correct all leaks at once.
6.
Reconnect heater and manual shutoff
valve to gas supply. Check reconnected
fittings for leaks.
Test Pressures Equal To or Less Than
1/2 PSIG
1.
Close manual shutoff valve (see Fig-
ure 22).
2.
Pressurize supply piping system by ei-
ther using compressed air or opening
propane/LP supply tank valve.
3.
Check all joints from propane/LP sup-
ply tank to manual shutoff valve (see
Figure 23). Apply mixture of liquid
soap and water to gas joints. Bubbles
forming show a leak.
4.
Correct all leaks at once.
Manual
Shutoff
Valve
Figure 22 - Manual Shutoff Valve
Propane/LP
Supply Tank
Figure 23 - Checking Gas Joints
14
®
HEATER
Pressure Testing Heater Gas
Connections
1.
Open manual shutoff valve (see Fig-
ure 22).
2.
Open propane/LP supply tank valve.
3.
Make sure control knob of heater is in
the OFF position.
4.
Check all joints from manual shutoff
valve to thermostat gas valve (see Fig-
ure 23). Apply mixture of liquid soap
and water to gas joints. Bubbles form-
ing show a leak.
5.
Correct all leaks at once.
6.
Light heater (see Operating Heater,
Open
O
pages 15 and 16). Check all other in-
POSI
ternal joints for leaks.
7.
Turn off heater (see To Turn Off Gas to
Appliance, page 15).
8.
Replace front panel.
PO
Closed
Thermostat Gas
Valve Location
Manual
Shutoff
Valve
103509