Venting Installation - Desa VC42NE SERIES Owner's Operation And Installation Manual

Direct-vent fireplace
Table of Contents

Advertisement

VENTING INSTALLATION

INSTRUCTIONS
Continued
INSTALLATION PLANNING
There are two basic types of direct-vent in-
stallation:
• Horizontal Termination
• Vertical Termination
Horizontal Termination Installation
IMPORTANT: Horizontal square terminations
require only inner portion of wall firestop. Hori-
zontal installations using round termination require
exterior portion of wall firestop (see Figure 14,
page 12).
1. Set the fireplace in its desired location and deter-
mine the route your horizontal venting will take.
Do not secure the fireplace until all venting has
been installed. Some installations require sliding
the fireplace in and out of position to make final
venting connections. Figures 14 through 18 on
pages 12 through 14 show different configura-
tions for venting with horizontal termination that
will help you decide which application best suits
your installation. Check to see if wall studs or
roof rafters are in the path of your desired vent-
ing route. If they are, you may want to adjust the
location of the fireplace.
2. Direct vent pipe sections and components are
designed with special twist-lock connections.
Twist-Lock Procedure:
the pipes have locking lugs (indentations).
These lugs will slide straight into matching
slots on the male ends of adjacent pipes.
Push pipe sections together and twist one
section clockwise approximately one-quar-
ter turn until the sections are fully locked
(see Figure 8). Note: Horizontal runs of vent
must be supported every three feet. Use wall
straps for this purpose.
3. Use a 45° elbow to connect venting system
to fireplace flue collar. The elbow is designed
to be twist-locked onto the flue collar as
described in step 2. IMPORTANT: Do not
attempt to alter the configuration of the elbow
by cutting, twisting, bending, etc.
4. Assemble the desired combination of pipe and
elbows to the fireplace flue collar. If there are
long portions of venting run, pre-assembled
pipe sections may be installed as subassem-
blies for convenience.
10
The female ends of
www.desatech.com
5. Carefully determine the location where the vent
pipe assembly will penetrate the outside wall.
The center of the hole should line up with the
center-line of the horizontal vent pipe. Mark the
wall for a 10
/
" x 10
3
4
frame the square hole in the exterior wall where
the vent will be terminated. If the wall being
penetrated is constructed of noncombustible
material, such as masonry block or concrete,
a 8
/
" hole with zero clearance is acceptable
1
2
(see Figure 9).
Female
Locking Lugs
Figure 8 - Vent Pipe Connections
Vent Opening
Combustible Wall
3
10
/
"
4
(273 mm)
3
10
/
"
4
(273 mm)
Vent Opening
Noncombustible Wall
1
8
/
"
2
(216 mm)
Figure 9 - Vent Opening Requirements
/
" square hole. Cut and
3
4
Male
Slots
3
10
/
" Inside Framing
4
(273 mm)
(Framing
Detail)
Center of
Hole
116237-01E

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vc42pe seriesVvc42ne seriesVvc42pe series

Table of Contents