Desa VC42NE SERIES Owner's Operation And Installation Manual page 15

Direct-vent fireplace
Table of Contents

Advertisement

VENTING INSTALLATION
INSTRUCTIONS
Continued
INSTALLATION FOR VERTICAL
TERMINATION
Note: Vertical restrictor must be installed in all
vertical installations.
1. Determine the route your vertical venting
will take. If ceiling joists, roof rafters or other
framing will obstruct the venting system,
consider an offset (see Figure 19) to avoid cut-
ting load bearing members. Note: Pay special
attention to these installation instructions for
required clearances (air space) to combustibles
when passing through ceilings, walls, roofs,
enclosures, attic rafters, etc. Do not pack air
spaces with insulation. Also note maximum
vertical rise of the venting system and any
maximum horizontal offset limitations.
2. Set the fireplace in desired location. Drop a
plumb line down from the ceiling to the posi-
tion of the fireplace exit flue. Mark the center
point where the vent will penetrate the ceiling.
Drill a small locating hole at this point.
Drop a plumb line from the inside of the roof
to the locating hole in the ceiling. Mark the
center point where the vent will penetrate the
roof. Drill a small locating hole at this point.
Wall Strap
Figure 19 - Offset with Wall Strap and 45°
Elbows
116237-01E
Roof Flashing
45° Elbow
Ceiling Firestop
www.desatech.com
Flat Ceiling Installation
1. Cut a 10
/
" square hole in the ceiling using
3
4
the locating hole as a center point. The opening
should be framed to 10
273 mm) inside dimensions, as shown in Figure
9 on page 10 using framing lumber the same size
as the ceiling joists. If the area above the ceiling
is an insulated ceiling or a room, nail firestop
from the top side. This prevents loose insulation
from falling into the required clearance space.
Otherwise, install firestop below the framed
hole. The firestop should be installed with no
less than three nails per side (see Figure 20).
2. Assemble the desired lengths of pipe and
elbows necessary to reach from the fireplace
flue up through the firestop. Be sure all pipe
and elbow connections are fully twist-locked
(see Figure 8, page 10).
3. Cut a hole in the roof using the locating hole
as a center point. (Cover any exposed open
vent pipes before cutting hole in roof.) The
10
/
" x 10
/
" hole must be measured on
3
3
4
4
the horizontal; actual length may be larger
depending on the pitch of the roof. There
must be a 1" clearance from the vent pipe to
combustible materials. Frame the opening as
shown in Figure 9, page 10.
4. Connect a section of pipe and extend up
through the hole.
Note: If an offset is needed to avoid obstruc-
tions, you must support the vent pipe every 3
feet. Use wall straps for this purpose (see Fig-
ure 19). Whenever possible, use 45° elbows
instead of 90° elbows. The 45° elbow offers
less restriction to the flow of the flue gases
and intake air.
If area above is a room or insulated area,
install firestop above framed hole.
If area above is not a room, install firestop
below framed hole.
Figure 20 - Installing Firestop
/
" x 10
/
" (273 mm x
3
3
4
4
15

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vc42pe seriesVvc42ne seriesVvc42pe series

Table of Contents