NOTICE: Read these instruc-
tions completely before attempt-
ing installation.
These models are tested and approved for
use with DESA Heating, LLC (direct-vent) pipe
components and terminations.
The venting system must terminate on the
outside of the structure and can not be at-
tached to a chimney or flue system serving a
separate solid fuel or gas burning appliance.
A direct-vent appliance must have its own
venting system. DO NOT common vent this
appliance.
These models are approved to be vented
either horizontally through an outside wall or
vertically through a roof or chase enclosure
using the following:
• When venting system terminates horizon-
tally on an outside wall, you may install
a standoff if the termination cap is to be
installed directly on a combustible finish
such as vinyl, wood, stucco, etc.
• Never run the vent downward as this may
cause excessive temperatures which could
cause a fire.
• Vent pipe air space clearances to com-
bustibles are 1" on all sides except on the
horizontal sections, which requires 2" clear-
ance from the top of the pipe. Where the
termination cap penetrates a combustible
wall, 1" air space clearance is required.
• Have fireplace and selected vent compo-
nents on hand to help determine the exact
measurements when elbowing or offsetting.
Always use wall firestops when penetrating
walls and firestops when penetrating ceil-
ings or attic spaces.
• If using a venting configuration of only
horizontal venting with no vertical run, a
1/4" rise for every 12" of run toward the
termination is required.
WARNING: Read all instruc-
tions completely and thoroughly
before attempting installation.
Failure to do so could result in
serious injury, property damage
or loss of life.
IMPORTANT: Do not seal vent cap to pipe.
Cap must be removable for servicing.
116035-01J

VENTING INSTALLATION

INSTALLATION pRECAUTIONS
• Wear gloves and safety glasses for pro-
• Use extreme caution when using ladders
• Be aware of electrical wiring locations in
The following actions will void the warranty
on your venting system:
• Installation of any damaged venting com-
• Unauthorized modification of the venting sys-
• Installation of any component part not
• Installation other than as instructed by
www.desatech.com
NOTICE: Failure to follow these in-
structions will void the warranty.
NOTICE: Do not seal termination
cap to vent pipe. Cap must be
removable for vent inspection
and maintenance.
tection
or when on roof tops
walls and ceilings
ponent
tem (Do not cut or alter vent components)
manufactured or approved by DESA
these instructions
WARNING: This gas fireplace
and vent assembly must be
vented directly to the outside.
The venting system must NEvER
be attached to a chimney serv-
ing a separate solid fuel burning
appliance. Each direct-vent gas
appliance must use a separate
vent system. Do not use com-
mon vent systems.
WARNING: vent pipe air
space clearances to combus-
tibles are 1" on all sides except
on the horizontal sections,
which require 2" clearances
from the top of the pipe. Where
the termination cap penetrates
a combustible wall, 1" air space
clearance is required.
11