The Fabricenter cabinet has the following power requirements:
Input voltage: 200 to 240 VAC.
Input current: 30.0 amps at 208 VAC.
Input frequency: 47 to 63 Hz.
The Fabricenter cabinet has the following cooling airflow and service
clearances.
Cooling airflow clearances:
Right and left side: No clearance required.
Front and rear: 15.2 centimeters (6.0 inches).
Service clearances:
Right and left side: No clearance required.
Front and rear: 91.4 centimeters (36.0 inches).
Figure A-1
illustrates the Fabricenter cabinet footprint. The bottom
denotes the front of the cabinet. The illustration includes:
1. Cabinet-leveling screws (eight total).
2. Cooling airflow cutouts (eight total).
3. Fibre Channel cable cutouts (two total).
4. Caster wheel attachments (four total).
5. Power cable cutout (one).