Power Requirements - McDATA StorageWorks 64 - SAN Director Switch Planning Manual

Fw 07.00.00/hafm sw 08.06.00 mcdata products in a san environment planning manual (620-000124-500, april 2005)
Hide thumbs Also See for StorageWorks 64 - SAN Director Switch:
Table of Contents

Advertisement

Power Requirements

McDATA products have the following nominal power requirements:
Intrepid 6064 Director:
Input voltage: 100 to 240 VAC.
Input current: 2.0 amps at 208 VAC.
Input frequency: 47 to 63 Hz.
Intrepid 6140 Director:
Input voltage: 200 to 240 VAC.
Input current: 4.2 amps at 208 VAC.
Input frequency: 47 to 63 Hz.
Intrepid 10000 Director:
Input voltage: 180 to 270 VAC.
Input current: 12.0 amps at 208 VAC.
NOTE: The Intrepid 10000 Director must be connected directly to facility
power outlets. The director draws a current of 32 amperes at power-on,
and must not be connected to power strips in the FC-512 Fabricenter
equipment cabinet.
Input frequency: 47 to 63 Hz.
Sphereon 3232 Switch:
Input voltage: 100 to 240 VAC.
Input current: 1.3 amps at 208 VAC.
Input frequency: 47 to 63 Hz.
Sphereon 4300 Switch:
Input voltage: 100 to 240 VAC.
Input current: 0.4 amps at 208 VAC.
Input frequency: 47 to 63 Hz.
Sphereon 4500 Switch:
Input voltage: 100 to 240 VAC.
Input current: 0.5 amps at 208 VAC.
Input frequency: 47 to 63 Hz.
Product Specifications