VENT-FREE PROPANE/LP BAY FRONT FIREPLACE
INSTALLATION
Continued
CONNECTING TO GAS
SUPPLY
WARNING: A qualified ser-
vice person must connect fire-
place to gas supply. Follow all
local codes.
CAUTION: Never connect
fireplace directly to the propane/
LP supply. This fireplace re-
quires an external regulator (not
supplied). Install the external
regulator between the fireplace
and propane/LP supply.
The installer must supply an external regu-
lator. The external regulator will reduce
incoming gas pressure. You must reduce
incoming gas pressure to between 11 and 14
inches of water. If you do not reduce incom-
ing gas pressure, fireplace regulator damage
could occur. Install external regulator with
the vent pointing down as shown in Figure
19. Pointing the vent down protects it from
freezing rain or sleet.
CAUTION: Use only new,
black iron or steel pipe. Inter-
nally-tinned copper tubing may
be used in certain areas. Check
your local codes. Use pipe of 1/2"
or greater diameter to allow
proper gas volume to fireplace. If
pipe is too small, undue loss of
pressure will occur.
Installation must include an equipment
shutoff valve, union, and plugged 1/8" NPT
tap. Locate NPT tap within reach for test
gauge hook up. NPT tap must be upstream
from fireplace (see Figure 20).
IMPORTANT: Install equipment shutoff
valve in an accessible location. The equip-
ment shutoff valve is for turning on or
shutting off the gas to the appliance.
For more information, visit www.desatech.com
CF26PR
Apply pipe joint sealant lightly to male
threads. This will prevent excess sealant
from going into pipe. Excess sealant in pipe
could result in clogged fireplace valves.
CAUTION: Use pipe joint seal-
ant that is resistant to liquid pe-
troleum (LP) gas.
Propane/LP
Supply
Tank
Figure 19 - External Regulator with Vent
Pointing Down
Figure 20 - Gas Connection
* Purchase the optional CSA design-certified equipment shutoff valve from your dealer. See
Accessories, page 28.
** Minimum inlet pressure for purpose of input adjustment.
We recommend that you install a sediment
trap in supply line as shown in Figure 20 .
Locate sediment trap where it is within
reach for cleaning. Install in piping system
between fuel supply and heater. Locate sedi-
ment trap where trapped matter is not likely
to freeze. A sediment trap traps moisture
and contaminants. This keeps them from
going into fireplace controls. If sediment
trap is not installed or is installed wrong,
fireplace may not run properly.
External
Regulator
Vent
Pointing
Down
Gas
Control
Approved Flexible
Gas Hose
3" Minimum
12
CSA Design-Certified
Equipment Shutoff Valve
With 1/8" NPT Tap*
From External
Regulator
(11" W.C.** to
14" W.C.
Pressure)
Cap
Pipe
Tee
Nipple Joint
Sediment Trap
105442