aIR FoR CoMBUsTIoN aNd VeNTIlaTIoN
vENTILATION AIR
Ventilation Air From Inside Building
This fresh air would come from an adjoining
unconfined space. When ventilating to an
adjoining unconfined space, you must provide
two permanent openings: one within 12" of the
ceiling and one within 12" of the floor on the
wall connecting the two spaces (see options
1 and 2, Figure 2). You can also remove door
into adjoining room (see option 3, Figure 2).
Follow the National Fuel Gas Code, ANSI
Z223.1/NFPA 54, Air for Combustion and
Ventilation for required size of ventilation
grills or ducts.
ventilation Air From Outdoors
Provide extra fresh air by using ventilation
grills or ducts. You must provide two perma-
nent openings: one within 12" of the ceiling
and one within 12" of the floor. Connect these
items directly to the outdoors or spaces open
to the outdoors. These spaces include attics
and crawl spaces. Follow the National Fuel
Gas Code, ANSI Z223.1/NFPA 54, Air for
Combustion and Ventilation for required size
of ventilation grills or ducts.
IMPORTANT: Do not provide openings for
inlet or outlet air into attic if attic has a thermo-
stat-controlled power vent. Heated air entering
the attic will activate the power vent.
NOTICE: This heater is intended
for use as supplemental heat.
Use this heater along with your
primary heating system. Do not
install this heater as your pri-
mary heat source. If you have a
central heating system, you may
run system's circulating blower
while using heater. This will help
circulate the heat throughout the
house. In the event of a power
outage, you can use this heater
as your primary heat source.
124002-01C
Continued
Ventilation
Grills into
Adjoining
Room,
Option 1
Figure 2 - Ventilation Air from Inside
Outlet
Air
Inlet
Air
Figure 3 - Ventilation Air from Outdoors

INsTallaTIoN

vice person must install heater.
Follow all local codes.
CHECK GAS TYPE
Use only the correct type of gas (natural or
propane/LP). If your gas supply is not the
correct gas type, do not install heater. Call
dealer where you bought heater for proper
type heater.
equipped for either natural gas
or propane/LP gas but not both.
Gas type is indicated on the rat-
ing plate. Field conversion is not
permitted.
www.desatech.com
Into Adjoining Room,
Or
Remove
Door into
Adjoining
Room,
Option 3
12"
Building
Ventilated
Outlet
Attic
Air
Inlet Air
WARNING: A qualified ser-
WARNING: This appliance is
12"
Ventilation Grills
Option 2
To Attic
To
Crawl
Space
Ventilated
Crawl Space