DeviceNet Remote I/O Communication Module RTU-DNET
2.3 DeviceNet Connection Port
The connector is used on the connection to DeviceNet. Wire by using the connector enclosed with RTU-DNET.
PIN
1
2
3
4
5
2.4 RUN/STOP Switch
RUN/STOP action
STOP → RUN
RUN → STOP
2.5 Address Switch
The switch is used on setting up the node address of RTU-DNET on DeviceNet. Range: 00 ~ 63 (64 ~ 99 are
forbidden).
Switch setting
0 ~ 63
64 ~ 99
Example: If you need to set the node address of RTU-DNET to 26, simply switch the corresponding switch of x10
to 2 and the corresponding switch of x10
Note:
Please set up the node address when the power is switched off. After the setup is completed, re-power
RTU-DNET.
When RTU-DNET is operating, changing the setting of node address will be invalid.
Use slotted screwdriver to rotate the switch carefully in case you scratch the switch.
2.6 Function Switch
The function switches are for:
Setting up data retention function (IN0)
Setting up the baud rate of DeviceNet (DR0 ~ DR1)
DR1
OFF
OFF
ON
ON
6
Signal
Color
V-
Black
CAN_L
Blue
SHIELD
CAN_H
White
V+
Red
1. Re-detecting the extension module.
2. Reading/writing the data in the extension
module.
Stop reading/writing the data in the extension
module.
Valid DeviceNet node address
Invalid DeviceNet node address
0
to 6.
DR0
Baud rate
OFF
125 kbps
ON
250 kbps
OFF
500 kbps
ON
Incorrect setting
Content
0 VDC
Signal-
-
Shielded
Signal+
24 VDC
Explanation
Content
5
4
3
2
1
RUN
STOP
5
0
5
0
DVP-PLC Application Manual
1