Power Supply and Ground
If the object size and field of vision are incompatible, use a standard CCTV
lens and light source.
SeeAlso
page 22
2-6
Power Supply and Ground
Wire the power supply and the ground to their respective terminals. Tighten
the screws to a torque of between 0.49 N¼m.
After wiring, confirm that the wiring is correct.
2-6-1
Crimp Terminals and Cables
The terminal block uses M3 terminal screws. Use appropriate crimp terminals
for M3 screws, as shown below.
6.2 mm max.
Applicable wire size: Insulated wire of 1.31 to 1.65 mm
2-6-2
Ground (Earth) Wiring
Always connect a ground wire to the F250's ground terminal. To avoid ground-
ing problems, do not share the ground wire with any other devices or wire the
ground to the building's steel framing.
Use a grounding point that is as close as possible and keep the ground wire as
short as possible.
• The lens has a fixed focal point. The actual field of vision and focal point
vary from lens to lens, so adjust the distance to the measurement object
after replacing the lens or camera.
• The camera mounting distance listed in the following tables is an approxi-
mate value. Mount the Camera so that the distance to the measurement
object can be adjusted easily.
Forked
W
Ground to 100
or less
Round
6.2 mm max.
Section 2-6
2
(AWG16 to AWG15)
19