Installation; Terminal Cover - Omron E5CSV Datasheet

Hide thumbs Also See for E5CSV:
Table of Contents

Advertisement

Installation

• All models in the E5CSV Series conform to DIN 43700 standards.
• The recommended panel thickness is 1 to 4 mm.
• Be sure to mount the E5CSV horizontally.
Mounting the E5CSV
1. For waterproof mounting, waterproof packing must be installed on the Controller. Waterproofing is not possible when group mounting several
Controllers.
2. Insert the E5CSV into the mounting hole in the panel.
3. Push the adapter from the terminals up to the panel, and temporarily fasten the E5CSV.
4. Tighten the two fastening screws on the adapter. Alternately tighten the two screws little by little to maintain a balance. Tighten the screws to a
torque of 0.29 to 0.39 N·m.
Dimensions
Note: All units are in millimeters unless otherwise indicated.
■ Controller
E5CSV
Hard Protective Cover
The Y92A-48B Protective Cover (hard type) is
available for the following applications.
°C
• To protect the set from dust and dirt.
• To prevent the panel from being accidentally
touched causing displacement of set values.
• To provide effective protection against water
92 A- 48
92 A- 48
92 A- 48
B
B
B
droplets.
Voltage output
models
Relay output
Alarm output
(See note 1.)
models
Voltage output
Relay output
1
1
1
6
12 VDC,
21 mA
2
2
2
7
A
3
3
8
B
4
4
9
B
5
5
10
Platinum resistance
Thermocouple
thermometer input
input
Thermocouple/
platinum resistance thermometer multi-input
Note: 1. The voltage output (12 VDC, 21 mA) is not electrically isolated from the internal circuits. When using a grounding thermocouple, do not
connect output terminals 1 or 2 to ground. Otherwise, unwanted current paths will cause measurement errors.
2. Models with 100 to 240 VAC and 24 VAC/VDC are separate. Models using 24 VDC have no polarity.
48×48
6
Note: Terminals cannot be removed.
Alarm output 1
100 to 240 VAC, 50/60 Hz
(24 VAC/VDC)
(See note 2.)
84
78
44.8×44.8
60 min.
Adapter for flush mounting
58
48
Note: 1. The recommended panel thickness is 1 to 4 mm.
2. Group mounting is possible in one direction only.

Terminal Cover

E53-COV10
Temperature Controllers
Panel Cutout Dimensions
+0.6
45
0
+0.6
+0.6
45
45
0
0
L = (48 × N−2.5)
Mounting side-by-side
(group mounting of N Controllers)
Y92F-30 Adapter for flush mounting
Panel
Tightening
screws
7.5
76.5
48
48.8
22
9.1
E5CSV
L
+1
0
3